- Terminal Board
- Isolated Safety Barriers
- Signal Isolators
- Surge Protective Devices
- Safety Relays
- Isolated Intelligent I/O Modules
- Intelligent Gateways
- Industrial Data Optical Transceivers
- Online Dew Point Analyzers
- Data Acquisition Modules
- HART data converter
PHD-11TP-11M PHD-12TP-111M
Overview
Specification
Specification
Input in hazardous area |
|
Signal type |
1) three wire PNP/NPN sensor input: |
2) Frequency signal input: | |
3) Proximity switch, dry contact switch input: | |
Output in safe area |
|
Output signal |
0~20mA、4~20mA、0~5V、0~10V |
Current output load resistance |
<350Ω |
Voltage output load resistance |
≥300Ω |
Basic parameters |
|
Power supply |
20~35V DC |
Power consumption |
≤85mA(24V power supply, 20mA output) |
Impulse width |
≥2μs |
Output accuracy |
0.1% F.S |
Temperature drift |
0.01% F.S/°C |
For details on the input signal fault detection function, refer to the applicable manual | |
Response time of relay |
20ms |
Working temperature |
-20°C~+60°C |
storage temperature |
-40°C~+80°C |
Relative humidity |
10%~95%RH (no condensation) |
EMC |
According to GB/T 18268(IEC 61326-1) |
Insulation strength |
Between intrinsically safe side and non-intrinsicallysafe side≥2500V AC/min |
Insulation resistance |
≥100MΩ(between input/output/power supply) |
Wire requirements |
Cross-section ≥0.5mm²;Insualtion strength ≥500V |
Installation place |
Installed in a safe zone, it can be connected to intrinsic safety instruments in hazardous areas up to Zone 0, IIC, Zone 20, and IIIC |
Applicable field equipments |
According to DIN19234 NAMUR proximity switch, dry contact switch etc. field devices (include intinsic pressure switch, temperature switch and luquid level switch etc.) , level impulse signal, three wire PNP/NPN sensor output, incremental encoder |
Safety certification |
|
Explosion-proof mark |
[Exia Ga] IIC [Exia Da] IIIC |
Explosion-proof standard |
GB/T 3836.1-2021、GB/T 3836.4-2021 |
Terminals 4-5 |
Um=250VAC/DC,Uo=10.5VDC,Io=14mA, |
Terminals 3-6 |
Um=250VAC/DC,Uo=14VDC,Io=8mA, |
Terminals 1-2-3 |
Um=250VAC/DC,Uo=17.5VDC,Io=330mA, |
Certification body |
Shanghai Inspection and Testing Institute of Instruments and Automation Systems (SITIIAS) |

Note:
1、PHD-11TP-11M does not include output part 2
2、The power rail function is an optional function, and users need to specify the power supply method when placing an order
The selection of power rail connectors can refer to page 89 of the "Annex"