- Terminal Board
- Isolated Safety Barriers
- Signal Isolators
- Surge Protective Devices
- Safety Relays
- Isolated Intelligent I/O Modules
- Intelligent Gateways
- Industrial Data Optical Transceivers
- Online Dew Point Analyzers
- Data Acquisition Modules
- HART data converter
0102030405
PHD-11TP-23
Overview
The frequency signal is input into the isolated safety barrier, which can realize the 1: 1 transmission of the frequency signal of the instrument in the dangerous area to the safe area, and provide the isolated power supply (12V or 24V) for the field instrument in the dangerous area. This product needs independent power supply, and the power supply, input and output are isolated between each other.
| Supply voltage | 20~35VDC, Power consumption: When powered by 24VDC and output at 12V level ≤ 70mA (PHD-11TP-23)
|
| Distribution voltage | Open circuit voltage ≤ 25V, distribution voltage ≥ 16V when loaded with 25mA (PHD-11TP-23) |
| Input signal |
Frequency ≤ 100kHz, amplitude ≤ 24V, duty cycle ≥ 20%,
high-level ≥ 4V, low-level ≤ 1V (PHD-11TP-23)
|
| Output signal |
Frequency 1: 1 output
Signal range: Signal low-level ≤ 0.5V Signal high level ≥ 20V (PHD-11TP-23)
|
| Number of input and output channels | 1 input 1 output |
| Applicable field equipments | Frequency measuring equipment |
| Temperature parameters | Working temperature: -20℃~+60℃, storage temperature:-40℃~+80℃ |
| Relative humidity | 10%~95% RH no condensation |
| Dielectric strength | Between intrinsically safe side and non-intrinsically safe side (≥ 3000VAC/min); between power supply and non-intrinsically safe terminal (≥ 1500VAC/min) |
| Insulation resistance | ≥100MΩ (between input/output/power supply) |
| Electromagnetic compatibility | According to IEC 61326-1(GB/T 18268), IEC 61326-3-1 |
| Explosion-proof mark | [Ex ia Ga] IIC [Ex ia Da] ⅢC |
| Certification Body | CQST(China National Quality Supervision and Test Centre for Explosion Protected Electrical Products) |
| Terminals 1-2 |
Um:250V AC/DC Uo=28V DC Io=93mA
Po=0.65W Co=0.05μF Lo=2.4mH
|
| Terminals 3-4 |
Um:250V AC/DC Uo=8V DC Io=2.5mA
Po=5mW Co=5.9μF Lo=100mH
|
| Installation site requirements | Installed in a safe zone, it can be connected to intrinsic safety instruments in hazardous areas up to Zone 0, IIC, Zone 20, and IIIC |
| MTBF | About 100000h |

Note: The power rail function is an optional function, and users need to specify
the power supply method when placing an order
The selection of power rail connectors can refer to page 89 of the "Annex"

PHD-11TC-33A-23