PHG-22TT Series
Overview
Thermocouple input temperature transmitter can isolate and convert
the DC signal from the thermocouple (TC) into a DC signal. This product
has a built-in cold junction compensation function and can be configured
intelligently. The actual range of the thermocouple can be set through
computer software. . It has the function of disconnection alarm and
out-of-range alarm function.
This product needs to be powered independently, and the power supply,
input and output terminals are isolated.
Input signal type and range table | ||||
Code | TC model | Measurement range | Minimum range | Conversion accuracy |
1 | K | -200~1370℃ | 50℃ | 0.5℃/0.1% |
2 | S | -50~1760℃ | 500℃ | 1.5℃/0.1% |
3 | E | -140~1000℃ | 50℃ | 0.5℃/0.1% |
4 | J | -160~1200℃ | 50℃ | 0.5℃/0.1% |
5 | B | 250~1800℃ | 500℃ | 1.5℃/0.1% |
6 | T | -200~400℃ | 50℃ | 0.5℃/0.1% |
7 | R | -50~1760℃ | 500℃ | 1.5℃/0.1% |
8 | N | -200~1300℃ | 50℃ | 0.5℃/0.1% |
Input | |
Input signal | K, S, E, J, B, T, R, N thermocouple signals (see "Input Signal Type and Range Table" for details) |
Input disconnection | The default "low alarm" can be modified to "high alarm" through configuration software |
Signal range | The measuring range of the corresponding thermocouple is -10~100mV. |
Measurement range | Users make their own configuration when ordering, and indicate it at the tail number or otherwise. |
Built-in cold compensation | ±1°C(Compensation range -20°C~ +60°C) |
Output: | |
Output signal | DC signal (current/voltage) |
Load Resistance | Current load resistance ≤500Ω (can be customized) Voltage load resistance <5mA (can be customized) |
Supply voltage | 20-35VDC |
Power consumption | Current output <0.8W; voltage output <1W |
LED indicator | Green: Power indicator Low range alarm L1 light on, high range alarm L2 light on |
Output accuracy | Please refer to the "Input Signal Type and Range Table" for details |
Response time | Reaching 90% of the final value within 300ms |
Temperature drift | 0.005%F.S/℃ |
Temperature parameters | Working temperature: -20℃~+60℃, storage temperature:-40℃~+80℃ |
Relative humidity | 10%~95% RH no condensation |
Dielectric strength | ≥2000VAC/min (between input/output/power supply) |
Insulation resistance | 100MΩ (500V DC)(between input/output/power supply) |
Electromagnetic compatibility | GB/T 18268,IEC 61326-1 |
MTBF | 80000h |
Wire requirements | Horizontal cutting surface ≥ 0.5mm2; Insulation strength ≥ 500V |
Applicable field equipments | K. S, E, J, B, T, R, N TC sensors |
Note: The power rail function is an optional function, and users need to specify
the power supply method when placing an order
The selection of power rail connectors can refer to page 89 of the "Annex"
For example: two inputs and two outputs, two thermocouple K (-200-1370C) inputs,
two 4-20mA outputs, 24V power supply, model: PHG-22TT-1111
PHD-11TC-33A-23