PHG-22TZ series
Overview
RTD input temperature transmitter can isolate and convert the thermal resistor (RTD) signal into a DC signal, which is used to drive the load. Intelligent configuration is possible, and the actual range of the thermal resistance can be set through computer software. It has the function of disconnection alarm and out-of-range alarm function.
This product needs to be powered independently, and the power supply, input and output terminals are isolated.
| Input | |
| Input signal | Two wire or three wire thermistor signals (see "Input Signal Type and Range Table" for details) |
| Input disconnection | The default "low alarm" can be modified to "high alarm" through configuration software |
| Signal range | Corresponding measurement range of thermal resistance |
| Measurement range | Users make their own configuration when ordering, and indicate it at the tail number or otherwise. |
| Excitation current | 800μΑ |
| Output: | |
| Output signal | DC signal (current/voltage) |
| Load capacity |
Current load resistance ≤500Ω (customizable)
Voltage load resistance <5mA (customizable)
|
| Basic parameters: | |
| Supply voltage | 20-35VDC |
| Power consumption | Current output <1.8W Voltage output <1W |
| LED indicator | Green: Power indicator Low range alarm yellow light on, high range alarm red light on |
| Output accuracy | Please refer to the "Input Signal Type and Range Table" for details |
| Response time | Reaching 90% of the final value within 300ms |
| Temperature drift | 0.005%F.S/℃ |
| Temperature parameters | Working temperature: -20℃~+60℃, storage temperature:-40℃~+80℃ |
| Relative humidity | 10%~95% RH no condensation |
| Dielectric strength | ≥2000VAC/min (between input/output/power supply) |
| Insulation resistance | 100MΩ(500VDC )(between input/output/power supply) |
| Electromagnetic compatibility | GB/T 18268(IEC 61326-1) |
| MTBF | 800000h |
| Wire requirements | Cross-section ≥ 0.5mm²; Insulation strength ≥ 500V |
| Applicable field equipments | Two wire or three wire thermistors G53, Cu50, Pt100, Pt1000, Ni1000 |

Note: 1. The power rail function is an optional function, and users need to specify the power supply method when placing an order.The selection of power rail connectors can refer to page 89 of the "Annex" 2. When inputting a three wire RTD, it is necessary to ensure that the three wires are of equal length as much as possible 3. When inputting a two-wire RTD, safety barrier terminals 5 and 6(2 and 3) must be short circuited
| Input signal type and range table | ||||
| Code | RTD model | Measurement range | Minimum range | Conversion accuracy |
| 1 | G53 | -50~150℃ | 20℃ | 0.2℃/0.1% |
| 2 | Cu50 | -50~150℃ | 20℃ | 0.2℃/0.1% |
| 4 | Pt100 | -200~850℃ | 20℃ | 0.2℃/0.1% |
| 6 | Pt1000 | -200~850℃ | 20℃ | 0.2℃/0.1% |
| 7 | Ni1000 | -60~250℃ | 20℃ | 0.2℃/0.1% |

For example: 2 inputs and 2 outputs, 2 channels thermal resistor Pt100 input, 2 channels 4~20mA output, 24V power supply, model is PHG-22TZ-4141
PHD-11TC-33A-23
PHG-22TZ