Overview
Thermocouple input temperature transmitter can isolate and convert the DC signal from the thermocouple (TC) into a DC signal. This product has a built-in cold junction compensation function and can be configured intelligently. The actual range of the thermocouple can be set through computer software. . It has the function of disconnection alarm and out-of-range alarm function.
This product needs to be powered independently, and the power supply, input and output terminals are isolated.
Parameters Definition | ||||
Code |
TC model |
Measurement range |
Minimum range |
Conversion accuracy |
1 |
K |
-200~1370℃ |
50℃ |
0.5℃/0.1% |
2 |
S |
-50~1760℃ |
500℃ |
1.5℃/0.1% |
3 |
E |
-140~ 1000℃ |
50℃ |
0.5℃/0.1% |
4 |
J |
-160~1200℃ |
50℃ |
0.5℃/0.1% |
5 |
B |
250~1800℃ |
500℃ |
1.5℃/0.1% |
6 |
T |
-200~400℃ |
50℃ |
0.5℃/0.1% |
7 |
R |
-50~1760℃ |
500℃ |
1.5℃/0.1% |
8 |
N |
-200~1300℃ |
50℃ |
0.5℃/0.1% |
| Input | |
| Input signal | K, S, E, J, B, T, R, N TC signals (see "Input Signal Type and Range Table" for details) |
| Input disconnection | The default "low alarm" can be modified to "high alarm" through configuration software |
| Signal range | The measuring range of the corresponding thermocouple is -10~100mV. |
| Measurement range | Users make their own configuration when ordering, and indicate it at the tail number or otherwise. |
| Built-in cold compensation | ±1°C(Compensation range -20°C~ +60°C) |
| Output: | |
| Output signal | DC signal (current/voltage) |
| Load Resistance | Current load resistance ≤500Ω (customizable)
Voltage load resistance <5mA (customizable) |
| Supply voltage | 20-35VDC |
| Power consumption | Current output <0.8W; voltage output <0.6W (PHG-11TT series) Current output <1.2W; voltage output <0.6W (PHG-12TT series) |
| LED indicator | Green: Power indicator Low range alarm L1 light on, high range alarm L2 light on |
| Output accuracy | Please refer to the "Input Signal Type and Range Table" for details |
| Response time | Reaching 90% of the final value within 300ms |
| Temperature drift | 0.005%F.S/℃ |
| Temperature parameters | Working temperature: -20℃~+60℃, storage temperature:-40℃~+80℃ |
| Relative humidity | 10%~95% RH no condensation |
| Dielectric strength | ≥2000VAC/min (between input/output/power supply) |
| Insulation resistance | 100MΩ (500V DC)(between input/output/power supply) |
| Electromagnetic compatibility | GB/T 18268,IEC 61326-1 |
| MTBF | 80000h |
| Wire requirements | Cross section ≥ 0.5mm2; Insulation strength ≥ 500V |
| Applicable field equipments | K. S, E, J, B, T, R, N TC sensors |