PHC-11TF-14
Overview
The switching output isolated safety barrier drives the on-site intrinsically safe equipment in the hazardous area through the contact switch and logic level signal control in the safe area. Thereby controlling solenoid valves, sound and light alarms, etc. The signal status indicator light is set in red and yellow colors, the alarm displays red, and the output solenoid valve and other working tasks display yellow.
This product needs to be powered independently, and the power supply, input and output terminals are isolated between each other.
| Supply voltage |
20~35V DC, Power consumption: ≤80mA(24V power supply,
when 12V/45mA power distribution)
|
| Input signal | Switch contact, logic level |
| Output signal | Open circuit voltage >24V, UE/IE=12.8V/45mA |
| Inversion function: K1 is set to the "ON" side, the circuit output is inverted. | |
| Alarm relay function | The dial switch K2 is set to the "ON" side, the circuit adopts the alarm function |
| Load Resistance< 50Ω, short-circuit alarm (SC), load resistance >10KΩ, open circuit alarm (LB) | |
| Alarm relay output characteristics | Response time: 20ms, driving capacity: 250VAC/2A, 30VDC/2A under resistive load |
| Number of input and output channels | 1 input 1 output |
| Applicable onsite equipments | Safety solenoid valve, audible and visual alarm |
| Temperature parameters | Working temperature: -20℃~+60℃, storage temperature:-40℃~+80℃ |
| Relative humidity | 10%~95% RH no condensation |
| Dielectric strength | Between intrinsically safe side and non-intrinsically safe side (≥ 3000VAC/min); between power supply and non-intrinsically safe terminal (≥ 1500VAC/min) |
| Insulation resistance | ≥100MΩ (between input/output/power supply) |
| External dimensions | Thickness 12.5mm x width 108mm x high 118mm |
| Electromagnetic compatibility | According to IEC 61326-1(GB/T 18268), IEC 61326-3-1 |
| Explosion-proof mark | [Ex ia Ga] IIC [Ex ia Da] ⅢC |
| Certification Body | CQST(China National Quality Supervision and Test Centre for Explosion Protected Electrical Products) |
| Authentication parameters (between terminals 3-4) | Um=250V Uo=28V Io=119mA Co=0.05μF Lo=2.1mH Po=0.83W |
| Installation site Requirements |
Installed in a safe zone, it can be connected to intrinsic safety instruments in hazardous areas up to Zone 0, IIC, Zone 20, and IIIC |

Note: The power supply of the power rail is an optional function. Users need to specify the power supply mode when ordering.