- Terminal Board
- Isolated Safety Barriers
- Signal Isolators
- Surge Protective Devices
- Safety Relays
- Isolated Intelligent I/O Modules
- Intelligent Gateways
- Industrial Data Optical Transceivers
- Online Dew Point Analyzers
- Data Acquisition Modules
- HART data converter
0102030405
PHD-12TZ-*11
Overview
Isolated safety barrier: PHD-12TZ-*11, RTD signal input, single input and dual output.
The isolated safety barrier can convert the RTD input signal in hazardous area to 4-20mA signal output and transmit it to the safe area. The circuit is equipped with single RTD signal input and DC dual output.
The output 4-20mA signal, can be intelligently configured. The actual range of RTD can be set by computer.
PHD-12TZ-*11, "*" indicates the input type of RTD, please use the code to indicate.
This product needs an external 20~35VDC power supply.
Input signal types and measurement range
Code | RTD model | Measurement range | Minimum range | Conversion accuracy |
1 | G53 | -50~150℃ | 20℃ | 0.2℃/0.1% |
2 | Cu50 | -50~150℃ | 20℃ | 0.2℃/0.1% |
4 | Pt100 | -200~850℃ | 20℃ | 0.2℃/0.1% |
6 | Pt1000 | -200~850℃ | 20℃ | 0.2℃/0.1% |
7 | Ni1000 | -60~250℃ | 20℃ | 0.2℃/0.1% |
Example: Isolated safety barrier Pt100 input, temperature range 0~400℃, with two outputs 4~20mA, power supply 20~35VDC, the model is PHD-12TZ-411 (0~400℃), the measurement range can be set to the specified range of 0~400℃ by computer
* Bus terminal power supply, please see appendix for details.
Specifications | |
Supply voltage | 20~35VDC, power consumption<1.8W(when power supply 24VDC, output 20mA) |
Input signal | Two-wire or three-wire RTD |
Output signal | 4~20mA |
Signal and measurement range | Signal range: corresponding to the measurement range of RTD |
Measurement range: When make an order, the user shall make the configuration by himself, which shall be indicated in the tail number or extra explained. | |
Allowable output load capacity | 0~500Ω(customizable) |
Alarm indication | L1 light is on at low-measurement range alarm; L2 light is on at high-measurement range alarm |
Channel number of input and output | 1 input 2 outputs |
Applicable field devices | 2-wire or 3-wire RTD(G53, Cu50, Pt100, Pt1000, Ni1000) |
Output accuracy | 0.1%F.S (Typical value: 0.05%F.S) |
Temperature drift | 0.005%F.S/℃ |
Temperature parameters | Working temperature: -20℃~+60℃, storage temperature:-40℃~+80℃ |
Relative humidity | 10%~95% RH no condensation |
Dielectric strength | Between intrinsically safe side and non-intrinsically safe side (≥ 3000VAC/min); between power supply and non-intrinsically safe terminal (≥ 1500VAC/min) |
Insulation resistance | ≥100MΩ (between input/output/power supply) |
External dimensions | Thickness 12.5mm x width 108mm x high 118mm |
Electromagnetic compatibility | According to IEC 61326-1(GB/T 18268), IEC 61326-3-1 |
Functional safety certification | SIL3 according to IEC 61508 EN 61511 standards |
Explosion-proof mark | [Exia Ga]IIC |
Certification Body | CQST(China National Quality Supervision and Test Centre for Explosion Protected Electrical Products) |
Certified parameters (between terminals 2-3-4) | Um=250V Uo=8.4V Io=31mA Co=4.8μF Lo=20mH Po=65mW |
Installation site requirements | It can be connected with instruments in 0 zone with ⅡA, ⅡB, ⅡC dangerous gas |
MTBF | ≤100000h |



PHD-11TC-33A-23