- HART data converter
- Isolated Safety Barriers
- Signal Isolators
- Surge Protective Devices
- Safety Relays
- Isolated Intelligent I/O Modules
- Intelligent Gateways
- Industrial Data Optical Transceivers
- Online Dew Point Analyzers
- Data Acquisition Modules
0102030405
PHC-22TD-1111
Overview
Isolated safety barrier at operating side: PHC-22TD-1111, dual input and dual output
with analog signal.
The safety barrier can transmit the 4~20mA signal from safe area to the dangerous
area, to drive the valve positioner, electric/gas converters and other actuators to work.
This product needs an external 20~35VDC power supply.
Terminal isolation between power supply, input and output.
Supply voltage | 20~35VDC, power consumption about 2W ( when 24 VDC power supply, output 20mA) |
Input signal | 4~20mA (HART) |
Output signal | 4~20mA (HART) |
Allowable output load capacity | 0~500 Ω |
Number of input and output channels | 2 inputs 2 outputs |
Applicable onsite equipments | Valve positioner, electric/pneumatic converter |
Temperature parameters | Working temperature: -20℃~+60℃, storage temperature:-40℃~+80℃ |
Relative humidity | 10%~95% RH no condensation |
Dielectric strength | Between intrinsically safe side and non-intrinsically safe side (≥ 3000VAC/min); between power supply and non-intrinsically safe terminal (≥ 1500VAC/min) |
Insulation resistance | ≥100MΩ (between input/output/power supply) |
External dimensions | Thickness 12.5mm x width 108mm x high 118mm |
Electromagnetic compatibility | According to IEC 61326-1(GB/T 18268), IEC 61326-3-1 |
Explosion-proof mark | [Exia Ga]IIC |
Certification Body | CQST(China National Quality Supervision and Test Centre for Explosion Protected Electrical Products) |
Authentication parameters (between terminals 1-2, 3-4) | Um=250V Uo=28V Io=93mA Co=0.05μF Lo=2.4mH Po=0.65W |
Installation site Requirements | It can be connected with instruments in 0 zone with ⅡA, ⅡB, ⅡC dangerous gas |
MTBF | About 100000h |
PHD-11TC-33A-23