PHC-22TD-1111
Overview
Ing analog output isolated safety barrier malyari yang maka-realize keng isolated transmission da reng 4~20mA signals ibat kareng instrumentu keng ligtas a lugal papunta keng delikadung lugal, mag-drive ya keng valve positioner, electric/pneumatic converter ampo aliwa pang kasangkapan keng site, ampo suportan ne ing bidirectional transmission da reng HART digital signals. Ing produktung ini mangailangan yang independenting power supply, at ing power supply, input ampo output makabukud la.
| Supply voltage | 20~35V DC, Power consumption: ≤90mA(power supply, 20mA output) |
| Input signal | 4~20mA (HART) |
| Output signal | 4~20mA (HART) |
| Lalaban keng karga | nung mag output yang 20mA, 0~800 Ω (customizable) |
| Bilang da reng input ampo output channels | 2 inputs 2 outputs |
| Applicable onsite equipments | Valve positioner, electric/pneumatic converter |
| Parameters ning temperatura | Temperatura ning obra: -20°C~+60°C, temperatura ning pamitipun:-40°C~+80°C |
| Relatibung humidity | 10%~95% RH alang condensation |
| Dielectric strength | pilatan ning intrinsically safe side ampo non-intrinsically safe side (≥ 3000VAC/min); pilatan ning suplay ning kuryenti ampo ing e ligtas a terminal (≥ 1500VAC/min) |
| Insulation resistance | ≥100MΩ (pilatan ning input/output/power supply) |
| Panlual a sukad | Kapal 12.5mm x lapad 108mm x katas 118mm |
| Electromagnetic compatibility | Agpang keng IEC 61326-1(GB/T 18268), IEC 61326-3-1 |
| Markang e malyaring sabog | [Ex ia Ga] IIC [Ex ia Da] ⅢC |
| Certification Body | CQST(China National Quality Supervision and Test Center for Explosion Protected Electrical Products) |
| Terminals 1-2, 3-4 | Um:250V AC/DC Uo=28V DC Io=93mA Po=0.65W Co=0.083μF Lo=4.2mH |
| Kailangan king lugal ning pamag-install | maka-install ya keng ligtas a lugar, malyari yang ikonekta keng intrinsic safety instruments keng delikadung lugal angga keng Zone 0, IIC, Zone 20, ampo IIIC |
| MTBF | mga 100000h |

Tandanan: Ing power supply ning power rail metung yang optional a function. kailangan da reng gagamit i-specify me ing power supply mode nung mag-order ka. Paki-refer me ing attachment keng bulung 89.



PHD-11TC-33A-23

PHC-22TD-1111