English
English Russian Chinese Simplified Chinese Traditional French German Portuguese Spanish Japanese Korean Arabic Irish Greek Turkish Italian Danish Romanian Indonesian Czech Afrikaans Swedish Polish Basque Catalan Esperanto Hindi Lao Albanian Amharic Armenian Azerbaijani Belarusian Bengali Bosnian Bulgarian Cebuano Chichewa Corsican Croatian Dutch Estonian Filipino Finnish Frisian Galician Georgian Gujarati Haitian Hausa Hawaiian Hebrew Hmong Hungarian Icelandic Igbo Javanese Kannada Kazakh Khmer Kurdish Kyrgyz Latin Latvian Lithuanian Luxembou.. Macedonian Malagasy Malay Malayalam Maltese Maori Marathi Mongolian Burmese Nepali Norwegian Pashto Persian Punjabi Serbian Sesotho Sinhala Slovak Slovenian Somali Samoan Scots Gaelic Shona Sindhi Sundanese Swahili Tajik Tamil Telugu Thai Ukrainian Urdu Uzbek Vietnamese Welsh Xhosa Yiddish Yoruba Zulu Kinyarwanda Tatar Oriya Turkmen Uyghur Abkhaz Acehnese Acholi Alur Assamese Awadish Aymara Balinese Bambara Bashkir Batak Karo Bataximau Longong Batak Toba Pemba Betawi Bhojpuri Bicol Breton Buryat Cantonese Chuvash Crimean Tatar Sewing Divi Dogra Doumbe Dzongkha Ewe Fijian Fula Ga Ganda (Luganda) Guarani Hakachin Hiligaynon Hunsrück Iloko Pampanga Kiga Kituba Konkani Kryo Kurdish (Sorani) Latgale Ligurian Limburgish Lingala Lombard Luo Maithili Makassar Malay (Jawi) Steppe Mari Meitei (Manipuri) Minan Mizo Ndebele (Southern) Nepali (Newari) Northern Sotho (Sepéti) Nuer Occitan Oromo Pangasinan Papiamento Punjabi (Shamuki) Quechua Romani Rundi Blood Sanskrit Seychellois Creole Shan Sicilian Silesian Swati Tetum Tigrinya Tsonga Tswana Twi (Akan) Yucatec Maya
Get Instant Quote
Leave Your Message
PHD-12HF-277
H Series Backplane Mounting Isolated Safety Barriers
Products Categories
Featured Products

PHD-12HF-277

Switch contact or Proximity switches (NAMUR) input/relay output


H Serie Backplane Mounting Isolated Safety Barriers
1 input 2 outputs

    Overview

    H serie backplane mounting isolated safety barriers at detection side: PHD-12HF-277, digital input and output, single input and dual output.
    The isolated barrier can convert the proximity switch and contact input in the hazardous area to the relay contact signal and transmit it to the safe area.
    The output relay is equipped with selection switch of "ON/OFF" situation. In addition, there is an input signal short-circuit or open-circuit alarm indication, the circuit provides power for the input sensor.
    This product needs independent power supply.
    The signal status indicator is set in red and yellow light to indicate the working status of the output relay, when it is for alarming then the light is red, during normal operation the light is yellow.

     

     

    Supply voltage 20~35VDC, power consumption<1.5W
    Input signal

    Switch contact or Proximity switches (NAMUR)

    Supply voltage of sensor on site 8V
    Signal input characteristics On-site input current: >2.1mA, it indication ON; On-site input current: <1.2mA, it indication OFF
    Output in safe area Response time: 20ms, driving capability: 250VAC/2A, 30VDC/2A under resistive load

    Output normally “Open”/“Closed”
    Contact conversion control

    When the dial switch K1, K3 is at "ON" side, the relay output is "OFF"
    When the dial switch K1, K3 is at "OFF" side, the relay output is "ON"
    When the dial switch K2, K4 is at "ON" side, the circuit selects indicating red light LFD alarm function
    LFD On-site input current>7mA, short-circuit alarm (SC) , on-site input current<0.1mA, open-circuit alarm ( LB)
    For switch contact input, when the disconnection detection function is required, a 22KΩ resistor must be connected parallel at both ends of the switch (Please see the switch contact II in the below wiring diagram)
    Number of input and output 1 input 2 outputs
    Applicable field equipments Dry contact or NAMUR proximity switch in accordance with DIN 19234 standard
    Temperature parameter Working temperature: -20℃~+60℃, storage temperature: -40℃~+80℃
    Relative humidity 10%~95% RH no condensation
    Dielectric strength Between intrinsically safe side and non-intrinsically safe side (≥3000VAC/min); between power supply and non-intrinsically safe terminal (≥1500VAC/min)
    Insulation resistance ≥100MΩ (between input/output/power supply)
    Dimensions Thickness 15.8mm * width 104.8mm * high 116.1mm
    Electromagnetic compatibility According to IEC 61326-1 (GB/T 18268), IEC 61326-3-1
    Explosion-proof mark [Exia Ga]IIC, [Exia Da]IIIC
    Certification body CQST(China National Quality Supervision and Test Centre for Explosion Protected Electrical Products)
    Certified parameters (between terminals 1-2)
    Um:250VAC/DC,Uo=10.5VDC,Io=14mA,
    Po=37mW,Co=2.4μF,Lo=165mH.
    Installation site requirements It can be connected with instruments in 0 zone with ⅡA, ⅡB, ⅡC dangerous gas

    Installed in a safe zone, it can be connected to intrinsic safety instruments in hazardous areas up to Zone 0, IIC, Zone 20, and IIIC

    MTBF ≤100000h