- Terminal Board
- Isolated Safety Barriers
- Signal Isolators
- Surge Protective Devices
- Safety Relays
- Isolated Intelligent I/O Modules
- Intelligent Gateways
- Industrial Data Optical Transceivers
- Online Dew Point Analyzers
- Data Acquisition Modules
- HART data converter
0102030405
PHL-T-BNC Network SPD(Video network)
Main characteristics
It can be used to protect LPZ0-LPZ2 and subsequent partition interfaces
Technical data
| Rated operating voltage Un | 5VDC |
| Maximum operating voltage Uc | 6VDC |
| Nominal working current IL | 500mA |
| Nominal discharge current In (8 / 20μs) | 10KA |
| The maximum discharge current (8 / 20μs) | 20kA |
| Lightning impulse voltage limp(10/350μs) | 2.5kA |
| Protection voltage Up (8/20μs) line to line | <45V |
| Protection voltage Up (8/20μs) line to ground | <600V |
| Band width | 30MHz |
| Insertion loss | <-0.5dB |
| Response time | <1ns |
| Housing material | Black aluminum |
| Workingtemperature range | -40℃~+80℃ |
| Installation method | DIN35mm |
| Grounding method | 1.5mm² grounding flexible wire, length 220mm |
| Test standard | GB/T/18802.21/IEC 61643-21 |

Schematic diagram

Dimension drawings