- HART data converter
- Isolated Safety Barriers
- Signal Isolators
- Surge Protective Devices
- Safety Relays
- Isolated Intelligent I/O Modules
- Intelligent Gateways
- Industrial Data Optical Transceivers
- Online Dew Point Analyzers
- Data Acquisition Modules
0102030405
PHG-12TD Series
Overview
PHG-12TD series analog input (output) signal isolator can isolate and
convert current or voltage signals into current or voltage signal output.
The input and output parameters can be customized according to
user needs.
This product needs to be powered independently, and the power supply,
input and output terminals are isolated.
Input | |
Input signal | DC signal(current/voltage) |
Input resistance | Voltage type ≥100kΩ Current type ≤100Ω |
Output | |
Output signal | DC signal(current/voltage) |
Load Resistance | Current load resistance ≤500Ω Voltage load resistance <5mA |
Basic parameters | |
Supply voltage | 20~35VDC |
Power consumption | Current output<1.2W Voltage output<0.5W |
LED indicator | Green: power indicator |
Output accuracy | 0.1%FS (Typical value: 0.05%F.S) |
Response time | 5ms to reach 90% of the final value |
Temperature parameters | Working temperature: -20℃ ~ +60℃, Storage temperature: -40℃ ~ +80℃ |
Relative humidity | 10%~95% RH no condensation |
Insulation strength | ≥2000VAC/min (input/output/power supply) |
Insulation resistance | ≥100MΩ (500V DC) (between input/output/power supply) |
Electromagnetic compatibility | GB/T 18268 (IEC 61326-1) |
MTBF | 80000h |
Wire requirements | cross section ≥ 0.5mm2; Insulation strength ≥ 500V |
Applicable field equipments | Current source, voltage source |
PHG-12TD Series