- Isolated Safety Barriers
- Signal Isolators
- Surge Protective Devices
- Safety Relays
- Isolated Intelligent I/O Modules
- Intelligent Gateways
- Industrial Data Optical Transceivers
- Online Dew Point Analyzers
- Data Acquisition Modules
- HART data converter
0102030405
PHG-11TC-33*
Overview
PHG-11TC-33* communication signal input signal isolator can realize two-way communication of RS-485 half-duplex digital signals in the control room and on-site. The circuit provides power distribution for on-site instruments (as shown in the table below).
This product needs to be powered independently, and the power supply, input and output terminals are isolated.
Code | Distribution voltage, current |
No | No distribution power |
A | 5V |
B | 6V |
C | 12V |
F | 24V |
H | Cutomizable |
Specifications
Input | |
Input signal | RS-485 Half Duplex Digital Signal |
Distribution power voltage | Provide distribution power 5V, 6V, 12V, 24V for field instruments |
Output: | |
Output signal | RS-485 Half Duplex Digital Signal |
Transmission delay | ≤10μs |
Transmission rate | ≤115.2kbps |
Supply voltage | 20-35VDC |
Power consumption | <4W (24V power supply, 5V/200mA power distribution) |
LED indicator |
Green: Power indicator Yellow: The control room transmits signals to the site Red: transmitting signals from the site to the control room |
Receiving and transmitting switching time | ≥20ms |
Temperature parameters | Working temperature: -20℃~+60℃ storage temperature:-40℃~+80℃ |
Relative humidity | 10%~95% RH no condensation |
Dielectric strength | ≥2000VAC/min(between input/output/power supply) |
Insulation resistance | 100MΩ(500 VDC) (between input/output/power supply) |
Electromagnetic compatibility | GB/T 18268(IEC 61326-1) |
MTBF | 800000h |
Wire requirements | Horizontal cutting surface ≥ 0.5mm2; Insulation strength ≥ 500V |
Applicable field equipments | Communication interface device with RS-485 Half Duplex Digital Signal |
Dimension
Schematic diagram
Note:
1. The power rail function is an optional function, and users need to specify the power supply method when placing an order
The selection of power rail connectors can refer to page 89 of the "Annex"