PHD-22HZ-*1*1
Overview
PHD-22HZ-*1*1, RTD signal input, dual input, and dual output constitute the isolated safety barrier.
The isolated safety barrier has the ability to transmit the 4/20mA signal output that is produced from the RTD input signal in the hazardous area to the safe area. The circuit has two RTD signal inputs and a DC double output.
The 4–20 mA output signal can be set up wisely. A computer can be used to set the real range of RTD.
PHD-22HZ-*1*1, where "*" denotes the RTD input type; please use the code to specify.
This product requires a separate power source.
Input signal types and measurement range
Code |
RTD model |
Measurement range |
Minimum range |
Conversion accuracy |
1 |
G53 |
-50~150℃ |
20℃
|
0.2℃/0.1% |
2 |
Cu50 |
-50~150℃ |
20℃
|
0.2℃/0.1% |
4 |
Pt100 |
-200~850℃ |
20℃
|
0.2℃/0.1% |
6 |
Pt1000 |
-200~850℃
|
20℃
|
0.2℃/0.1% |
7 |
Ni1000 |
-60~250℃ |
20℃
|
0.2℃/0.1% |
Example: Isolated safety barrier Pt100 input, temperature range 0~400℃, two outputs are with 4~20mA, the
power supply is 20~35VDC. The model is PHD-22HZ-4141 (0~400℃), the measurement range can be set to the
specified range of 0~400℃ by computer.
RTD input/4~20mA output (configurable) 2 inputs 2 outputs
Supply voltage | 20~35VDC, power consumption<2W (when power supply 24VDC, output 20mA) |
Input signal | Two-wire or three-wire RTD |
Output signal | 4~20mA |
Signal and measurement range | Signal range: corresponding to the measurement range of RTD |
Measurement range: When make an order, the user shall make the configuration by himself, which shall be indicated in the tail number or extra explained | |
Allowable output load capacity | 0~500Ω (customizable) |
Alarm indication | L1 light is on at low-measurement range alarm; L2 light is on at high-measurement range alarm |
Channel number of input and output | 2 inputs 2 outputs |
Applicable field devices | 2-wire or 3-wire RTD (G53, Cu50, Pt100, Pt1000, Ni1000) |
Output accuracy | 0.1%F.S (Typical value: 0.05%F.S) |
Temperature drift | 0.005%F.S/℃ |
Temperature parameters | Working temperature: -20℃~+60℃, storage temperature: -40℃~+80℃ |
Relative humidity | 10%~95% RH no condensation |
Insulation strength | Between intrinsically safe side and non-intrinsically safe side (≥3000VAC/min); |
between power supply and non-intrinsically safe side (≥1500VAC/min) | |
Insulation resistance | ≥100MΩ (between input/output/power supply) |
External dimensions | Thickness 15.8mm * width 104.8mm * high 116.1mm |
Electromagnetic compatibility | According to IEC 61326-1 (GB/T 18268), IEC 61326-3-1 |
Explosion-proof mark | [Exia Ga]IIC |
Certification body | CQST (China National Quality Supervision and Test Centre for Explosion Protected Electrical Products) |
Certified parameters | Um=250V Uo=8.4V Io=31mA Co=4.8μF Lo=20mH Po=65mW |
(between terminals 4-5-6.1-2-3) | |
Installation site requirements | It can be connected with instruments in 0 zone with ⅡA, ⅡB, ⅡC dangerous gas |
MTBF | ≤100000h |