PHD-22HZ-*1*1
Overview
Input signal types and measurement range
|
Code |
RTD model |
Measurement range |
Minimum range |
Conversion accuracy |
|
1 |
G53 |
-50~150℃ |
20℃
|
0.2℃/0.1% |
|
2 |
Cu50 |
-50~150℃ |
20℃
|
0.2℃/0.1% |
|
4 |
Pt100 |
-200~850℃ |
20℃
|
0.2℃/0.1% |
|
6 |
Pt1000 |
-200~850℃
|
20℃
|
0.2℃/0.1% |
|
7 |
Ni1000 |
-60~250℃ |
20℃
|
0.2℃/0.1% |
Main technical parameters |
|
Number of channels: |
two inputs and two outputs |
Power supply: |
|
Power supply voltage: |
20~35V DC, power consumption of about 2W (24V DC, output 20mA) |
Power protection: |
power reverse protection |
Hazardous side input: |
|
Input Signal: |
2-wire or 3-wire RTD signal (see "Input Signal Type and Range Table") |
Signal range: |
Corresponding to the measuring range of RTDs. |
Measuring range: |
the user to develop their own configuration when ordering, specified in the end number or other instructions |
Safety side output: |
|
Output signal: |
4~20mA |
Allowable Output Load Capacity: |
0~500Ω (Customizable) |
LED indicator: |
Green ⸺Power indicator; L1 light on for low range alarm; L2 light on for high range alarm. |
Output accuracy: |
See "Input signal type and range table". |
Response time: |
300ms to 90% of final value |
Temperature Drift: |
0.005%F.S/°C |
Temperature parameters: |
operating temperature -20℃~+60℃; storage temperature -40℃~+80℃ |
Air relative humidity: |
10%~95%RH without condensation |
Insulation strength: |
intrinsically safe end and non-intrinsically safe end (≥3000V AC/min); between power supply and non-intrinsically safe (≥1500V AC/min) |
Insulation resistance: |
≥100MΩ (input/output/power supply between) |
Electromagnetic compatibility: |
in line with IEC 61326-1 (GB/T 18268), IEC 61326-3-1 |
Mean time to failure: |
100000 hours |
Wire requirements: |
cross-section ≥ 0.5mm2; insulation strength ≥ 500V |
Applicable field devices: |
2-wire or 3-wire RTD G53, Cu50, Pt100, Pt1000, Ni1000 |
Installation site: |
installed in the safe zone, can be connected with the highest in Zone 0, IIC, Zone 20, IIIC hazardous locations of the intrinsically safe instrumentation |
Safety certification |
|
Certification body: |
National Explosion-proof Electrical Product Quality Supervision and Testing Center CQST |
Certification standard: |
GB/T 3836.1-2021, GB/T 3836.4-2021 |
Explosion-proof symbol: |
[Exia Ga]ⅡC, [Exia Da]ⅢC |
Certified parameters (between terminals 1-2): |
Um:250VAC/DC,Uo=8.4VDC,Io=31mA, |