English Russian Chinese Simplified Chinese Traditional French German Portuguese Spanish Japanese Korean Arabic Irish Greek Turkish Italian Danish Romanian Indonesian Czech Afrikaans Swedish Polish Basque Catalan Esperanto Hindi Lao Albanian Amharic Armenian Azerbaijani Belarusian Bengali Bosnian Bulgarian Cebuano Chichewa Corsican Croatian Dutch Estonian Filipino Finnish Frisian Galician Georgian Gujarati Haitian Hausa Hawaiian Hebrew Hmong Hungarian Icelandic Igbo Javanese Kannada Kazakh Khmer Kurdish Kyrgyz Latin Latvian Lithuanian Luxembou.. Macedonian Malagasy Malay Malayalam Maltese Maori Marathi Mongolian Burmese Nepali Norwegian Pashto Persian Punjabi Serbian Sesotho Sinhala Slovak Slovenian Somali Samoan Scots Gaelic Shona Sindhi Sundanese Swahili Tajik Tamil Telugu Thai Ukrainian Urdu Uzbek Vietnamese Welsh Xhosa Yiddish Yoruba Zulu Kinyarwanda Tatar Oriya Turkmen Uyghur Abkhaz Acehnese Acholi Alur Assamese Awadish Aymara Balinese Bambara Bashkir Batak Karo Bataximau Longong Batak Toba Pemba Betawi Bhojpuri Bicol Breton Buryat Cantonese Chuvash Crimean Tatar Sewing Divi Dogra Doumbe Dzongkha Ewe Fijian Fula Ga Ganda (Luganda) Guarani Hakachin Hiligaynon Hunsrück Iloko Pampanga Kiga Kituba Konkani Kryo Kurdish (Sorani) Latgale Ligurian Limburgish Lingala Lombard Luo Maithili Makassar Malay (Jawi) Steppe Mari Meitei (Manipuri) Minan Mizo Ndebele (Southern) Nepali (Newari) Northern Sotho (Sepéti) Nuer Occitan Oromo Pangasinan Papiamento Punjabi (Shamuki) Quechua Romani Rundi Blood Sanskrit Seychellois Creole Shan Sicilian Silesian Swati Tetum Tigrinya Tsonga Tswana Twi (Akan) Yucatec Maya
立即获取报价
Leave Your Message
PHD-12TZ-466+
温度输入
产品类别
特色产品

PHD-12TZ-466+

浪涌保护类型:RTD输入隔离安全屏障

1 个输入 2 个输出

输入:两线或三线制RTD Pt100信号

输出:RTD Pt100信号

    概述

    该热敏电阻输入隔离安全屏障具有浪涌保护功能,可将危险区域内两线制和三线制热敏电阻(RTD)的Pt100信号转换为热敏电阻的1:1信号,并将其传输至安全区域。它可进行智能配置,热阻的实际测量范围可通过计算机软件进行设置。该产品具有断线报警和超量程报警功能。本产品需要独立电源,并采用隔离式电源、输入和输出端子。

     

    1

     

    输入
    输入信号 两线或三线Pt100信号
    测量范围 -150℃~850℃
    输出:
    输出信号 RTD Pt100信号
    浪涌保护功能:
    标称放电电流 ln(8/20μs) 5kA
    电压保护等级 Up(8/20μs): 60V(线电压)
    电压保护等级 Up(8/20μs): 600V(线对地)
    根据标准 GB/T18802.21-2016(相当于 1EC61643-21:2012)
    供电电压 20-35VDC
    功耗 ≤55mA(24VDC电源供电时)
    LED指示灯 绿色:电源指示灯
    短路报警:ALM 红灯长时间亮起
    开路报警:ALM 红灯闪烁
    输出精度 0.1%FS
    温度漂移 0.1%FS/10℃
    温度参数 工作温度:-20℃~+60℃,存储温度:-40℃~+80℃
    相对湿度 相对湿度10%~95% 无冷凝
    绝缘强度 本质安全侧与非本质安全侧之间≥2000VAC/min(≥3000VAC/min);电源与非本质安全侧之间≥1500VAC/min
    绝缘电阻 ≥100MΩ(输入/输出/电源之间)
    电磁兼容性 根据 IEC 61326-1(GB/T 18268)、IEC 61326-3-1
    平均故障间隔时间 800000小时
    电线要求 横截面积≥0.5mm²;绝缘强度≥500V
    适用现场设备 两线或三线 RTD Pt100



    1

    注:1. 电源轨功能为可选功能,用户需要指定。
    下单时的供电方式
    电源轨连接器的选择可参考“附件”第 89 页。
    2. 输入三线制热电阻时,必须确保三根导线连接正确。
    尽可能使各根电线长度相等
    3. 输入两线制热电阻时,安全栅端子 6 和 5 必须连接。
    短路