SPECIFICATIONS
Technical data |
Katangian ning suplay ning kuryenti: |
Suplay ning kuryenti: | 24V DC |
Kasalukuyan a pamangailangan: | ≤ 35mA (24V DC, para keng balang chnnel) |
Voltage range: | 16V~35V DC |
Input characteristics: |
Input current: | ≤ 35mA (24V DC ) |
Wire resistance: | ≤ 15 Ω |
Input device: | SIS controller DI/DO signals |
Output characteristics: |
Bilang da reng akasabi: | 2ALI |
Materyal a gamitan: | AgSnO2 |
Excontact fuse protection: | 5A (Internal) |
Contact capacity: | 5A/250V AC; 5A/24V DC |
Mechanical lifespan: | maygit 107oras |
Katangian ning oras: |
Switch-on delay : | ≤ 30ms |
Delay-on de-energisation: | ≤ 30ms |
Oras ning pamagbawi: | ≤ 30ms |
Magsupply short interruption: | 20ms |
sertipikasyun ning kaligtasan
Safety Integrity Level (SIL): | SIL3 makayagpang ya keng IEC 61508 |
Hardware Fault Tolerance(HFT): | 0 makayagpang ya keng IEC 61508 |
Safe failure fraction(SFF): | 99% makayagpang ya keng IEC 61508 |
Probability ning hazardous failure (PFHd): | 1.00E-09/h makayagpang ya keng IEC 61508 |
StopCategory: | 0 makayagpang ya keng EN 60204-1 |
10% average a bilang da reng hazardous failure cycles da reng components (B10d): |
Rated Voltage 24VDC ampo L/R=7ms : | Ie 2A 1A 0.5A |
Cycles 180,000 300,000 400,000 |
Rated Voltage 230VAC cos φ= At 0.4: | Ie 2A 1A 0.5A |
Cycles 500,000 580,000 600,000 |
Katangian ning kapaligiran
Electromagnetic compatibility | conforms to EN 60947, EN 61000-6-2, EN 61000-6-4 |
Vibration frequency | 10Hz~55Hz |
Vibration amplitude | 0.35mm |
temperatura ning paligid | -20 °C~+60 °C |
temperatura ning pamitipun | -40 ℃~+85 ℃ |
Relatibung humidity | 10% anggang 90% |
Altitude | ≤ 2000m |
katangian ning insulation
Electrical clearance ampo creepage distance: | agpang keng EN 60947-1 |
Overvoltage level: | III |
Antas ning polusyun: | 2 |
Antas ning proteksyun: | IP20 |
Lakas ning insulasyon: | 1500V AC, 1 minutu |
Rated insulation voltage: | 250V AC |
Rated impulse voltage: | 6000V (1.2/50us) |
Panlual a sukad

Kapal 114.5mm * katas 99mm * lapad 22.5mm
Wiring diagram

Functional Block Diagram

tipikal a aplikasyun

Wiring diagram

(1) Ing instrument wiring mag adopt yang Pluggable connecting terminal ;
(2) Ing malambut a tansu a cross-sectional area ning input side wire dapat mas maragul ya kesa 0.5mm2, at ing output side dapat mas maragul ya kesa 1mm2;
(3) Ing makabuklat a kaba ning kawad mga 8mm ya, na makakandadu kareng M3 screws;
(4) Deng output contacts kailangan lang mamye sapat a fuse protection connections;
(5) Ing copper conductor dapat makayabut ya keng temperaturang e kumulang keng 75 °C;
(6) Deng terminal screws malyari lang maging sangkan ning misoperation, pamangisnawa, atbp. Uli na niti, pakihigpitan me agpang keng makasulat a torque. Terminal screw tightening torque 0.5Nm.
Install

Deng safety relays dapat lang i-install kareng control cabinets na ating at least IP54 protection level.
Ing PH6002-2A series safety relays maka-install la ngan keng DIN35mm guide rails. Deng steps ning pamag install ilapin deng makatuki
(1) I-clamp ing babo nang dake ning instrumentu keng guide rail;
(2) Itulak me ing lalam nang dake ning instrumentu keng guide rail.
Pamaglako

Para ilako ing instrument panel, tukian la deng steps a reni:
(1)Isulud me ing screwdriver a maki lapad a 6mm o mas ditak pa keng metal a latch a atyu keng lalam ning instrument panel.
(2)Itulak me ing distornilyador patas kabang sabay-sabay meng i-pry ing metal latch pababa. Ing aksyon ayni makabuklat ya keng latch.
(3)Kabang makabuklat ya ing latch, maingat meng iguyud ing instrument panel patas at palual keng guide rail.
nung tukian me deng steps a reni, malyari meng ligtas at epektibung ilako ing instrument panel keng guide rail para keng maintenance o inspection.
Atensyun
Oreni ing pamagpatune kareng impormasyun a binie:
(1) Pamagbalot ning Produktu, Modelu ning Label, at Detalyasyun: I-verify nung ing packaging ning produktu, modelu ning label, ampo ding detalye makayagpang la kareng makasulat keng kontrata ning pamamili.
(2)Pag-ingat Bayu I-install at Gamitan: Siguraduan na deng gagamit maingat lang mamasa keng manual bayu la mag-install ampo gamitan deng safety relays para aintindian da ing operational guidelines ampo ing safety precautions.
(3)Impormasyun para keng Technical Support: Ing Beijing Pinghe Technical Support Hotline, a akit keng 400 711 6763, dapat yang akit para keng nanu mang kutang o saup.
(4) Kapaligiran ning Pamag-install: I-install me ing safety relay keng control cabinet na ating minimum a IP54 protection level para protektan ya kareng environmental factors.
(5)Power Supply Requirements: Ing instrumentu mag operate ya keng 24V power supply. importanti ing iwasan ing pamangamit 220V AC power supply para aiwasan ing pangasira o pangasira.
Ing pamanuki kareng tuntunan a reni makasaup para makasiguradung ligtas at ustu ing pamag-install, pamag-operate, ampo pamag-maintain ning safety relay system.
Ayusan
(1) Paki-check regular nung ing safety function ning safety relay atyu ya keng masanting a kondisyun, ampo nung atin yang tanda na ing circuit o ing original me-tamper ya o me-bypass ya;
(2) Paki tukian la reng kaugnayan a regulasyun ning kaligtasan at mag operate agpang kareng instruksiun na niting instruction manual, nung ali malyari yang magdalang makamate a aksidenti o pangawala da reng tau at pibandian;
(3) Ding produktu dinalan lang mahigpit a pamagsuri at pamagkontrol king kalidad bayu la meko king pabrika. nung akit mu na ali la gagana deng produktu ampo magduda kang atin yang depektu ing internal module, pakisabi me ing pekamalapit a ahente o diretsu kang makipag ugnayan keng technical support hotline.
(4) Kilub ning anam a banua manibat keng petsa ning pamagdeliver, ding sablang problema keng kalidad ning produktu keng normal a pamangamit dapat yang ayusan ning Pinghe alang bayad.