English Russian Chinese Simplified Chinese Traditional French German Portuguese Spanish Japanese Korean Arabic Irish Greek Turkish Italian Danish Romanian Indonesian Czech Afrikaans Swedish Polish Basque Catalan Esperanto Hindi Lao Albanian Amharic Armenian Azerbaijani Belarusian Bengali Bosnian Bulgarian Cebuano Chichewa Corsican Croatian Dutch Estonian Filipino Finnish Frisian Galician Georgian Gujarati Haitian Hausa Hawaiian Hebrew Hmong Hungarian Icelandic Igbo Javanese Kannada Kazakh Khmer Kurdish Kyrgyz Latin Latvian Lithuanian Luxembou.. Macedonian Malagasy Malay Malayalam Maltese Maori Marathi Mongolian Burmese Nepali Norwegian Pashto Persian Punjabi Serbian Sesotho Sinhala Slovak Slovenian Somali Samoan Scots Gaelic Shona Sindhi Sundanese Swahili Tajik Tamil Telugu Thai Ukrainian Urdu Uzbek Vietnamese Welsh Xhosa Yiddish Yoruba Zulu Kinyarwanda Tatar Oriya Turkmen Uyghur Abkhaz Acehnese Acholi Alur Assamese Awadish Aymara Balinese Bambara Bashkir Batak Karo Bataximau Longong Batak Toba Pemba Betawi Bhojpuri Bicol Breton Buryat Cantonese Chuvash Crimean Tatar Sewing Divi Dogra Doumbe Dzongkha Ewe Fijian Fula Ga Ganda (Luganda) Guarani Hakachin Hiligaynon Hunsrück Iloko Pampanga Kiga Kituba Konkani Kryo Kurdish (Sorani) Latgale Ligurian Limburgish Lingala Lombard Luo Maithili Makassar Malay (Jawi) Steppe Mari Meitei (Manipuri) Minan Mizo Ndebele (Southern) Nepali (Newari) Northern Sotho (Sepéti) Nuer Occitan Oromo Pangasinan Papiamento Punjabi (Shamuki) Quechua Romani Rundi Blood Sanskrit Seychellois Creole Shan Sicilian Silesian Swati Tetum Tigrinya Tsonga Tswana Twi (Akan) Yucatec Maya
Krieg ‘n direk offerte
Leave Your Message
PH6002-2A Intelligent veiligheidsrelais
SIS-systeemveiligheidsrelais
Produktcattegorieje
Beoordeilde produkte

PH6002-2A Intelligent veiligheidsrelais

Overzich

PH6002-2A is un geavanceerde veiligheidsrelaiscontrolemodule die speciaal is oontwikkeld veur ut isolere en umzètte vaan DI/DO-signale binne Safety Instrumented Systems (SIS). Mit twie betroubare normaal open (NO) kontakte, zörg ‘t veur naadloze integratie en werking binne kritieke veiligheidsinstellinge.

Dees module, ontworpe mit efficiëntie en gemak in de gaten, besjikt euver gereserveerde terminale die snelle offline Proof Test-procedures vergemekeleke, onderhoudsprocesse stroumliene en stilstand minimalisere.

Intern umvat de module geavanceerde Fail-safe-technologie, triple redundancy-technologie en contactfusie-besjermingstechnologie. Dees innovatieve functies zörge veur de maximale betrouwbaarheid en veiligheid door potentiële foute te detectere en te vermindere, en door kritieke operaties in gevierleke umgevinge te bewaore.

PH6002-2A is ‘n betrokke oplossing veur veulendige veiligheidstoepassinge, en beejt gemoedsrust en complianceverzekering veur zoewel operateurs es organisaties.

    SPECIFICATIES

    Technische data

    Kenmerke vaan de voedingsvoorziening:

    Stroomveurziening:

    24V DC

    Huidig ​​verbruuk:

    ≤ 35mA (24V DC, veur eder kanaal)

    Spanningsbereik:

    16V~35V DC

    Invoerkenmerke:

    Invoerstroum:

    ≤ 35mA (24V DC )

    Draadweerstand:

    ≤ 15 Ω

    Invoerapparaat:

    SIS-controller DI/DO-signale

    Oetvoerkenmerke:

    Aontal contacte:

    2NO

    Contactmateriaal:

    AgSnO2

    Besjerming vaan contactzekeringe:

    5A (Intern)

    Contactcapaciteit:

    5A/250V AC; 5A/24V DC

    Mechanische levesduur:

    mie es 107keer

    Tiedkenmerke:

    Aansjakelvertraging :

    ≤ 30ms

    Vertraging op de-energisatie:

    ≤ 30ms

    Hersjteltied:

    ≤ 30ms

    Korte oonderbreking vaan levering:

    20ms

    veiligheidscertificaat

    Veiligheidsintegriteitsniveau (SIL):

    SIL3 voldoet aan IEC 61508

    Hardware Fault Tolerance (HFT):

    0 voldoet aan IEC 61508

    Veilige mislukkingsfractie (SFF):

    99% voldoet aan IEC 61508

    Kans op gevaarlijk foute (PFHd):

    1.00E-09/h voldoet aan IEC 61508

    StopCategorie:

    0 voldoet aan EN 60204-1

    10% gemiddeld aantal gevaarlike foutcyclusse vaan oonderdeile (B10d):

    Nominale spanning 24VDC en L/R=7ms :

    Ie 2A 1A 0,5A

    Cycli 180.000 300.000 400.000

    Nominale spanning 230VAC cos φ= Op 0,4:

    Ie 2A 1A 0,5A

    Cycli 500.000 580.000 600.000

    Milieukenmerke

    Elektromagnetische compatibiliteit

    voldoet aan EN 60947, EN 61000-6-2, EN 61000-6-4

    Trillingsfrequentie

    10Hz~55Hz

    Trillingsversterking

    0,35mm

    Omgevingstemperatuur

    -20 ℃~+60 ℃

    Opsjlaagtemperatuur

    -40 ℃~+85 ℃

    Relatieve vochtigheid

    10% tot 90%

    Huugte

    ≤ 2000m

    Isolatiekenmerke

    Elektrische klaring en kruupafsjtand:

    in overeenstemming mit EN 60947-1

    Euverspanningsniveau:

    III

    Vervuilingsniveau:

    2

    Besjermingsniveau:

    IP20

    Isolatiesterkte:

    1500V AC, 1 minuut

    Nominale isolatiespanning:

    250V AC

    Nominale impulsspanning:

    6000V (1.2/50us)

    Externe afmetinge

    PH6002-2A8dhg

    Dikte 114,5 mm * hoogte 99 mm * breedte 22,5 mm

    Bedradingsdiagram

    PH6002-2A7s9h5

    Functioneel blokdiagram

    PH6002-2A90lk

    Typische toepassing

    PH6002-2A101ky

    Bedradingsdiagram

    Externe afmetinge 49xg
    (1) De bedrading vaan ‘t instrumint gebruuk ‘n insteekbare verbindingsklemme;
    (2) De zachte kopere dwarsdoorsjnee vaan de invoerkantdraad mot groeter zien es 0,5 mm2, en de oetvoerkant mot groeter zien es 1 mm2;
    (3) De blootgestelde lengte vaan de draod is ongeveer 8mm, dee is vergrendeld door M3-sjroeve;
    (4) De oetgangscontacte motte voldoende zekeringsbesjermingsverbindinge veurzien;
    (5) Kopere geleider moot ‘n umgevingstemperatuur vaan ten minste 75 °C weerstaan;
    (6) Klemtsjroeve kinne veroorzake tot verkeerde werking, verhitting, enz. Draai ‘t daorum aan volgens ‘t opgegeve koppel. Aansjpanningskoppel vaan de klemsjroef 0,5Nm.

    Installatie

    Externe afmetinge6n1n
    Veiligheidsrelais motte weure geïnstalleerd in controlekasten mit op z’n mins IP54 besjermingsniveau.
    De PH6002-2A-serie veiligheidsrelais zien allemaol geïnstalleerd mit DIN35mm geleidingsrails. De installatie stappe zien de volgende
    (1) Klem ‘t bovekant vaan ‘t instrumint op de geleidingsrail;
    (2) Druk ‘t oonderste eind vaan ‘t instrumint in de geleidingsrail.

    Demanteling

    Externe dimensies5ria
    Volg dees stappe um ‘t instrumentpaneel te verwijdere:
    (1) Steek ‘n schroevedraaier mit ‘n mesbreidte vaan 6mm of minder in de metaole vergrendeling aon ‘t oonderste eind vaan ‘t instrumintepaneel.
    (2)Druk de schroevedraaier nao bove onderwieles dat ge tegeliekertied de metale vergrendeling nao oonder drejt. Deze actie zal de vergrendeling losmake.
    (3) Mit de vergrendeling losgekoppeld, trek ut instrumintepaneel veurzichtig umhoeg en oet de geleidingsrail.
    Door dees stappe te volge, kins se ‘t instrumentpaneel veilig en effectief oet de geleidingspoor verwijdere veur oonderhouds- of inspectiedoeleinde.

    Opgelit

    Hei is un verificatie vaan de verstrekte informatie:
    (1)Productverpakking, etiketmodel en specificaties: Controleer of de produkverpakking, etiketmodel en specificaties euvereinkomme mit de in ‘t aankoopcontract gesjreve.
    (2)Veurzörgsmaotregele veur installatie en gebruuk: Zörg d’r veur dat gebruukers de handleiding zorgvuldig leze veurtot ze veiligheidsrelais installere en gebruke um de bedriefsriechlijne en veiligheidsveurzörgsmaotregele te begriepe.
    (3) Contactgegevens veur technische ondersteuning: De Beijing Pinghe technische ondersteuning hotline, bereikbaar op 400 711 6763, moot weure gecontacteerd veur vraoge of hulp.
    (4)Installatie-umgeving: Installeer ‘t veiligheidsrelais in ‘n bedieningskast mit ‘n minimum IP54-besjermingsniveau um ‘t te besjerme tege umgevingsfactore.
    (5) Voorzieningsvereiste: ‘t instrumint wèrk op ‘n 24V voeding. ‘t Is cruciaal um ‘t gebruuk vaan ‘n 220V AC-voeding strik te vermijde um sjaoj of stoornisse te veurkómme.
    ‘t Volge vaan dees riechlijne helpt um de veilige en gooje installatie, bediening en oonderhoud vaan ‘t veiligheidsrelaysysteem te garandere.

    Onderhoud

    (1) Controleer regelmaotig of de veiligheidsfunctie vaan ‘t veiligheidsrelais in gooje staot is, en of d’r tekens zien dat ‘t circuit of ‘t origineel is gemanipuleerd of umgegoon;
    (2) Volg de relevante veiligheidsregels en werk volgens de instructies in deze instructiehandleiding, aanders kin ut leie tot dodelike óngelökke of ‘t verlies vaan personeel en bezit;
    (3) De produkte höbbe strikte inspectie en kwaliteitscontrole ondergaon veurtot ze de febrik verlaote. Es geer óntdek dat de producte neet good wèrke en vermoedt dat de interne module foutief is, neem daan contact op mit de dichtstbijzijnde agent of direk contact opnumme mit de technische hulplijn.
    (4) Binne zes jaor vanaaf de datum vaan levering, motte alle productkwaliteitsprobleme tijdens normaal gebruuk gratis door Pinghe were gerepareerd.