- Terminal Board
- Makabukud a Safety Barriers
- Signal Isolators
- Surge Protective Devices
- Safety Relays
- Isolated Intelligent I/O Modules
- Intelligent Gateways
- Industrial Data Optical Transceivers
- Online Dew Point Analyzers
- Data Acquisition Modules
- HART data converter
0102030405
PH D-22T F-2727
Overview
Isolated safety barrier keng detection side: PHD-22TF-2727, digital input ampo output, dual input ampo dual output.
Ing makabukud a barrier malyari neng i-convert ing proximity switch ampo ing contact input keng delikadung lugal keng relay contact signal ampo i-transmit ne keng ligtas a lugal.
Ing output relay atin yang selection switch ning "ON/OFF" a sitwasyun. Dagdag pa, atin yang input signal short-circuit o open-circuit alarm indication, ing circuit mamye yang kuryenti para keng input sensor.
Ing produktung ini mangailangan yang panlual a 20-35VDC a suplay ning kuryenti.
Ing signal status indicator maka set ya keng red ampo yellow a sulu para ipabalu ing working status ning output relay, nung para ya keng alarming kanita ing sulu mapula ya, kabang normal yang operasyun ing sulu yellow ya.
* Bus power supply, lawan me ing appendix para kareng detalye.
| Supply voltage | 20~35VDC, power consumption |
| Input signal | Palitan ing contact/proximity switch |
| Supply voltage ibat keng sensor side keng site | 8V |
| katangian ning signal input | On-site input current: >2.1mA, buri ng sabyan ON; on-site input current: |
| Switch hysteresis: 0.2ms | |
| Relay output characteristics | Response time: 20ms, driving capacity: 250VAC/2A, 30VDC/2A lalam ning resistive load. |
| Output "ON"/"OFF" contact conversion control | Nung ing dial switch K1, K3 atyu ya keng "ON" side, ing relay output "OFF" ya. |
| Nung ing dial switch K1, K3 atyu ya keng "OFF" a gilid, ing relay output atyu ya keng "ON". | |
| Nung ing dial switch K2, K4 atyu ya keng "ON" a gilid, ing circuit mamili yang magpakit a red light relay alarm function. | |
| magpakit keng sulu ning alarm function | On-site input current > 7mA, short-circuit alarm (SC), on-site input current |
| Para keng switch contact input, nung kailangan ing disconnection detection function, ing 10KΩ resistor kailangan yang makakonekta parallel kareng adwa nang wakas ning switch (Paki lawan me ing switch contact II keng wiring diagram king lalam) | |
| Bilang ning input ampo output | 2 input 2 output |
| Applicable field equipments | Dry contact o NAMUR proximity switch agpang keng DIN 19234 standard. |
| Parameter ning temperatura | Temperatura ning obra: -20°C- +60°C, temperatura ning pamitipun: -40°C- +80°C |
| Relatibung danum ning angin | 10%~95%RH alang condensation |
| Dielectric strength | pilatan ning intrinsically safe side ampo non-intrinsically safe side (≥ 3000VAC/min); pilatan ning suplay ning kuryenti ampo ing e ligtas a terminal (≥ 1500VAC/min) |
| Insulation resistance | ≥100MΩ (pilatan ning input/output/power supply) |
| Panlual a sukad | Kapal 12.5mm x lapad 108mm x katas 118mm |
| Electromagnetic compatibility | Agpang keng IEC 61326-1(GB/T 18268), IEC 61326-3-1 |
| Markang e malyaring sabog | [Exia Ga]IIC |
| Sertipikasyun ning kaligtasan a pang-obra | SIL3 agpang keng IEC 61508 EN 61511 standards |
| Certification Body | CQST(China National Quality Supervision and Test Center for Explosion Protected Electrical Products) |
| Certified parameters (pilatan da reng terminal 3-4,1-2) | Um=250V Uo=10.5V I=15mA Co=1.7μF Lo=150mH Po=39.4mW |
| Kailangan king lugal ning pamag-install | Malyari yang ikonekta kareng instrumentu keng 0 zone a maki IIA, IIB, IIC delikadung gas |
| MTBF | ≤100000h |







PHD-11TC-33A-23

PHD-22TF-2727