PHD-12TZ-461
Overview
Ing thermistor input isolation safety barrier malyari yang i-convert ing Pt100 signals da reng adwang wire ampo atlung wire thermistor (RTDs) kareng delikadung lugal keng metung a output a maki 1:1 RTD signal ampo metung a output a maki 4~20mA signal papunta keng safety zone. Malyari yang i-configure king matalino, at ing tutuking range ning thermal resistance malyari yang i-set kapamilatan ning computer software.
Ing produktung ayni mangailangan yang independenting power supply, a maki makabukud a power supply, input, ampo output terminals.
| Detalyadu | |
| Input keng delikadung lugar | |
| Input signal | Adwang kawad o atlung kawad RTD Pt100 signal |
| Sukat ning sukad | -200°C-850°C |
| Safety side output: | |
| Output signal | RTD Pt100 signal ampo 4~20mA signal |
| Kapasidad ning karga | Load capacity 0-500 Ω (customizable) |
| Supply voltage | 20-35VDC |
| Pamangamit king kuryenti | ≤76mA (nung 24VDC power supply, output 20mA) |
| LED indicator | Green: Power indicator |
| Katuliran ning pamaglual | 0.1%FS |
| Ing pamagbayu ning temperatura | 0.1%FS/10°C |
| Parameters ning temperatura | Temperatura ning obra: -20°C~+60°C, temperatura ning pamitipun:-40°C~+80°C |
| Relatibung humidity | 10%~95% RH alang condensation |
| Dielectric strength | pilatan ning intrinsically safe side ampo non-intrinsically safe side (≥ 3000VAC/min); |
| pilatan ning suplay ning kuryenti ampo ing e ligtas a terminal (≥ 1500VAC/min) | |
| Insulation resistance | ≥100MΩ (pilatan ning input/output/power supply) |
| Electromagnetic compatibility | Agpang keng IEC 61326-1(GB/T 18268), IEC 61326-3-1 |
| MTBF | 100000h |
| kailangan ing kawad | Cross section ≥ 0.5mm2; Insulation strength ≥ 500V |
| Applicable field equipments | Duwang kawad o atlung kawad RTD Pt100 |
| Lugar ning pamag-install | Maka-install ya keng safe zone, malyari yang ikonekta kareng intrinsic safety instruments kareng hazardous a lugal angga keng Zone 0, IIC, Zone 20, ampo IIIC |
| Sertipikasyun ning kaligtasan | |
| Markang e malyaring sabog | [Ex ia Ga]lIC [Ex ia Da]lllC |
| Pamantayan a e makasabog | GB/T3836.1-2021 GB/T3836.4-2021 |
| Terminals 4-6、5-6 | Um:250V AC/DC Uo=8.4V DC lo=31mA |
| Po=65.1mW Co=4.8μF Lo=20mH | |
| katawan ning sertipikasyun | CQST(China National Quality Supervision and Test Center for Explosion Protected Electrical Products) |

Tandanan: 1. Ing power rail function metung yang optional a function, at kailangan lang i-specify deng gagamit ing paralan ning suplay ning kuryenti nung mag order ka
Ing pamili kareng power rail connectors malyari yang akit keng page 89 ning "Annex"
2. Potang mag input kang atlung kawad a RTD, kailangan mung siguraduan na ing atlung parehu la kaba deng kawad angga keng malyari
3. Potang mag input kang two-wire RTD, ing safety barrier terminals 6 ampo 5 dapat me short circuited