- Terminal Board
- Makabukud a Safety Barriers
- Signal Isolators
- Surge Protective Devices
- Safety Relays
- Isolated Intelligent I/O Modules
- Intelligent Gateways
- Industrial Data Optical Transceivers
- Online Dew Point Analyzers
- Data Acquisition Modules
- HART data converter
0102030405
PHD-12TF-277+
Overview
Ing isolated safety barrier a maki surge protection function ning switch input relay outputs, na mag isolate ampo mag transmit input signals ibat kareng switch contacts o proximity switches kareng delikadung lugal papunta keng safety zone a maki output relay kapamilatan ning safety barrier. Ing line fault detection malyari ya kapamilatan ning metung a relay output at mipalabas ya keng babo ning LED ning module. Ing dial switch ning module magagamit ya para i-set ing input ampo output in-phase o reverse control, ampo para i-enable o i-disable ing line fault detection alarm indication function.
Ing produktung ayni mangailangan yang independenting power supply, a maki makabukud a power supply, input, ampo output terminals.
| Input keng delikadung lugar | |
| Input signal | Palitan la reng contact/proximity switches |
| Ing supply voltage ning sensor | Manga 8V |
| Switching rate | |
| Input/output characteristics: | |
| keng site input current | >2.1mA, ing output makasara ya, papakit na ON; Nung |
| Ing output normal yang "Open"/"Closed" Contact conversion control | Nung ing dial switch K1, K3 atyu ya keng "ON" side, ing relay output "Normally closed" ya. Nung ing dial switch K1K3 atyu ya keng "OFF" side, ing relay output "Normally open" ya. Nung ing dial switch K2K4 atyu ya keng "ON" side, ing circuit mamili yang magpakit a red light LFD alarm function |
| Output keng ligtas a lugal | |
| Output signal | Relay |
| Kapasidad ning pamagmaneho | 250VAC/2A,30VDC/2A nung mipailalam ya kareng resistive loads |
| oras ning pakibat | 20ms |
| Surge protection features: | |
| Nominal discharge current ln(8/20μs) | 5kA |
| Voltage protection level Up(8/20μs): | 60V(line to line) |
| Voltage protection level Up(8/20μs): | 600V(line to ground) |
| Agpang kareng pamantayan | GB/T18802.21-2016(equivalent to 1EC61643-21:2012) |
| Basic parameters | |
| Supply voltage | 20~35VDC |
| Pamangamit king kuryenti | |
| LED indicator | Berde: Power indicator Yellow: Output relay keng normal a gagawan a Pula: LFD indication, line fault alarm |
| Parameters ning temperatura | Temperatura ning obra: -20°C ~ +60°C, Temperatura ning pamitipun: -40°C ~ +80°C |
| Relatibung humidity | 10%~95% RH alang condensation |
| Lakas ning insulasyon | pilatan ning intrinsically safe side ampo non-intrinsically safe side (≥3000VAC/min); pilatan ning suplay ning kuryenti ampo ing e ligtas a gilid (≥1500VAC/min) |
| Insulation resistance | 100MΩ(500V DC) (pilatan ning input/output/power supply) |
| Electromagnetic compatibility | GB/T 18268 (IEC 61326-1) |
| MTBF | 80000h |
| kailangan ing kawad | Cross section ≥ 0.5mm2; Insulation strength ≥ 500V |
| Applicable field equipments | Deng kasangkapan keng field antimo reng dry contacts o NAMUR type proximity switch inputs na makayagpang keng DIN19234 standard |

Tandanan: Ing power supply ning power rail metung yang optional a function. kailangan da reng gagamit
i-specify me ing power supply mode nung mag-order ka.
Paki-refer me ing attachment keng page 89.
Line Fault Detection(LFD)
Malyari deng pilinan deng gagamit ing "ON" a gilid ning switch keng babo ning module
para a-enable ing fault detection function ampo para ipabalu ing alarm kapamilatan ning
red LED light. keng site input current>7mA, short circuit alarm (SC);
keng site input current
contact input mangailangan yang fault detection function (wire breakage, short
circuit), ing 22k Ω resistor dapat makakonekta ya parallel kareng adwang wakas
ning switch, at ing 680 Ω resistor dapat yang makakonekta keng serye (antimo
akakit ya keng wiring diagram para keng switch contact II).

PHD-11TC-33A-23