- Tabula Terminalis
- Claustra Salutis Isolata
- Isolatores Signorum
- Instrumenta ad Impetus Protegendos
- Releis Salutis
- Moduli I/O Intelligentes Isolati
- Portae Intelligentes
- Transceptores Optici Datorum Industrialium
- Analysores Puncti Roris Interretialis
- Moduli Acquisitionis Datorum
- Conversor datorum HART
PHD-12HT-*11
Conspectus
Tabula Typi et Ambitus Signi Ingressus | ||||
Codex | Modelus Thermocouple | Spatium Mensurae | Spatium minimum | Accuratio Conversionis |
1 | K | -200~1370℃ | 50℃ | 0.5℃ / 0.1% |
Duo | S | -50~1760℃ | 50℃ | 1.5℃ / 0.1% |
Tres | ET | -140~1000℃ | 50℃ | 0.5℃ / 0.1% |
quattuor | I. | -160~1200℃ | 500℃ | 0.5℃ / 0.1% |
quinque | B. | 250~1800℃ | 50℃ | 1.5℃ / 0.1% |
sex | T. | -200~400℃ | 500℃ | 0.5℃ / 0.1% |
VII | R | -50~1760℃ | 50℃ | 1.5℃ / 0.1% |
VIII | N. | -200~1300℃ | 500℃ | 0.5℃ / 0.1% |
Parametri technici principales |
|
Numerus canalium: | unus ingressus et duo exitus |
Fons potentiae: |
|
Tensio potentiae: | 20~35V DC, consumptio potentiae circiter 1.8W (24V DC, egressus 20mA) |
Protectio potentiae: | praesidium inversum potentiae |
Ingressus lateris periculosi: |
|
Signum Ingressus: | Signa thermocouple K, S, E, J, B, T, R, N (vide "Tabulam Typorum et Spatiorum Signorum Ingressus") |
Ambitus signalis: | Correspondens ambitu mensurae thermocoupli -10~100mV. |
Spatium mensurae: | Usui ut propriam configurationem evolvat cum iubet, in numero finali vel aliis instructionibus specificatam. |
Compensatio finis frigidi inclusa: | ±1℃ (intervallum compensationis -20℃~+60℃) |
Exitus lateris securitatis: |
|
Signum egressus: | 4~20mA |
Capacitas Oneris Producti Permissa: | 0~500Ω (Configurabilis) |
Indicator LED: | Viridis ⸺ Indicator potentiae; lumen L1 accensum pro alarmi intervalli inferioris; lumen L2 accensum pro alarmi intervalli superioris. |
Accuratio exitus: | Vide "Tabulam generis et ambitus signi ingressus". |
Tempus responsionis: | 500ms ad 90% valoris finalis |
Deviatio Temperaturae: | 0.005% FS/°C |
Parametri temperaturae: | temperatura operandi -20℃~+60℃; temperatura repositionis -40℃~+80℃ |
Humiditas relativa aeris: | 10%~95% RH sine condensatione |
Robur insulationis: | extremum intrinsece tutum et extremum non intrinsece tutum (≥3000V AC/min); inter fontem potentiae et finem non intrinsece tutum (≥1500V AC/min) |
Resistentia insulationis: | ≥100MΩ (inter input/output/power supply) |
Compatibilitas electromagnetica: | secundum IEC 61326-1 (GB/T 18268), IEC 61326-3-1 |
Tempus medium ad defectum: | Decem milia horarum |
Requisita filorum: | sectio transversalis ≥ 0.5mm2; robur insulationis ≥ 500V |
Instrumenta campi applicabilia: | Instrumenta in agro applicabilia: sensores thermocouple K, S, E, J, B, T, R, N |
Locus institutionis: | In zona tuta installatum, cum summis in locis periculosis Zonae 0, IIC, Zonae 20, IIIC instrumentorum intrinsece tutorum coniungi potest. |
Certificatio securitatis |
|
Corpus certificationis: | Centrum Nationale Supervisionis et Probationis Qualitatis Productorum Electricorum Explosionibus Resistentium (CQST) |
Norma certificationis: | GB/T 3836.1-22021, GB/T 3836.4-2021 |
Symbolum explosionis immune: | [Exia Ga]ⅡC, [Exia Da]ⅢC |
Parametri probati (inter terminales 1-2): | Um: 250V AC/DC, Uo = 8.4V DC, Io = 31mA, |