Cantonese
English Russian Chinese Simplified Chinese Traditional French German Portuguese Spanish Japanese Korean Arabic Irish Greek Turkish Italian Danish Romanian Indonesian Czech Afrikaans Swedish Polish Basque Catalan Esperanto Hindi Lao Albanian Amharic Armenian Azerbaijani Belarusian Bengali Bosnian Bulgarian Cebuano Chichewa Corsican Croatian Dutch Estonian Filipino Finnish Frisian Galician Georgian Gujarati Haitian Hausa Hawaiian Hebrew Hmong Hungarian Icelandic Igbo Javanese Kannada Kazakh Khmer Kurdish Kyrgyz Latin Latvian Lithuanian Luxembou.. Macedonian Malagasy Malay Malayalam Maltese Maori Marathi Mongolian Burmese Nepali Norwegian Pashto Persian Punjabi Serbian Sesotho Sinhala Slovak Slovenian Somali Samoan Scots Gaelic Shona Sindhi Sundanese Swahili Tajik Tamil Telugu Thai Ukrainian Urdu Uzbek Vietnamese Welsh Xhosa Yiddish Yoruba Zulu Kinyarwanda Tatar Oriya Turkmen Uyghur Abkhaz Acehnese Acholi Alur Assamese Awadish Aymara Balinese Bambara Bashkir Batak Karo Bataximau Longong Batak Toba Pemba Betawi Bhojpuri Bicol Breton Buryat Cantonese Chuvash Crimean Tatar Sewing Divi Dogra Doumbe Dzongkha Ewe Fijian Fula Ga Ganda (Luganda) Guarani Hakachin Hiligaynon Hunsrück Iloko Pampanga Kiga Kituba Konkani Kryo Kurdish (Sorani) Latgale Ligurian Limburgish Lingala Lombard Luo Maithili Makassar Malay (Jawi) Steppe Mari Meitei (Manipuri) Minan Mizo Ndebele (Southern) Nepali (Newari) Northern Sotho (Sepéti) Nuer Occitan Oromo Pangasinan Papiamento Punjabi (Shamuki) Quechua Romani Rundi Blood Sanskrit Seychellois Creole Shan Sicilian Silesian Swati Tetum Tigrinya Tsonga Tswana Twi (Akan) Yucatec Maya
攞即時報價
Leave Your Message
PHC-11TF-36 PHC-22TF-3636
數碼輸出
產品類別
精選產品

PHC-11TF-36 PHC-22TF-3636

PHC-11TF-361輸入1輸出

PHC-22TF-3636 2 輸入 2 輸出

輸入:接觸控制直流電壓

輸出:開關輸出驅動 12V (60mA)

    概覽

    12V/60mA 開關輸出隔離安全屏障,透過接觸開關控制,將電力由安全區域傳送到危險區域,驅動電磁閥同聲音 / 視覺警報等本質安全現場裝置。安全區域嘅輸入側係透過觸點連接到電源。

     

    PHC-11TF-36 PHC-22TF-363612

    規格

     

    喺安全區域輸入

     

    輸入訊號

    接觸控制直流電壓

    受控電源

    20 ~ 35VDC ,功耗約2.5W / 通道

    喺危險區域輸出

     

    輸出訊號

    開關輸出驅動 12V (60mA)

    開路輸出電壓

    22V ~ 24V

    警報繼電器功能

    將浸開關 K1( K2)設定為「 ON 」側,然後選擇通道 - (通道2)電路嘅警報功能
    當負載電阻
    當負載電阻 > 10k Ω 時,開路警報( LB )

    回應時間

    ≤20毫秒

    駕駛能力

    250V 交流 / 2A ,30V 直流 / 2A

    載入類型

    電阻負荷

    基本參數

     

    LED 指示燈

    CH :通道指示燈
    警報:警報指示燈

    溫度參數

    工作溫度: -20 ° C ~ + 60 ° C
    儲存溫度: -40 ° C ~ + 80 ° C

    相對濕度

    10 % ~ 95 % RH 冇結露

    絕緣強度

    本質安全邊同非本質安全邊之間( ≥ 3000V AC/min )

    絕緣電阻

    ≥ 100M Ω (輸入 / 輸出 / 電源之間)

    EMC

    根據 IEC 61326-1( GB/T 18268)同 IEC 61326-3-1

    接線要求

    斷面 ≥ 0.5mm2,絕緣強度 ≥ 500V

    適用嘅野外設備

    聲音/視覺警報,本質安全嘅電磁閥

    安裝地點

    佢安裝喺安全區,可以連接到危險區域嘅內在安全儀器,最高可達 0 區、 IIC 、 20 區同 IIIC 區

    安全認證

     

    防爆標記

    [前到加] IIB [前到達] IIIC

    防爆標準

    GB/T 3836.1-2021,GB/T 3836.4-2021

    端子參數2-3、5-6

    Um = 250V 交流 / 直流, Uo = 25.2V DC , Io = 170mA ,
    Po = 1.07W , Co = 0.82uF , Lo = 4mH

    認證機構

    CQST (中國國家防爆電氣產品質量監督測試中心)


    PHC-11TF-36 PHC-22TF-3636

    注意: PHC-11TF-36唔包括輸入2同輸出2部分


    下載檔案
    博士-11TC-33A-23