Overview
Frequency input signal isolator, i-convert me ing frequency signal keng input end keng DC signal output keng safety barrier agpang keng range a set ning user.
Ing produktung ini kailangan yang independenting powered, at ing power supply, input ampo output makabukud la king metung at metung.
| Detalyadu | |
| Input keng delikadung lugar | |
| Frequency signal input | Input frequency:0.1Hz~100kHz Maximum allowable input voltage:30Vp-p Minimum input level: 2V,(2Hz~100kHz) 2V,(0.1Hz~100kHz) |
| Output keng ligtas a lugal | |
| Output signal | 0~20mA、4~20mA、0~5V、0~10V |
| Ing kasalukuyan a lulwal a pamaglaban king karga | ≤350Ω |
| Voltage output load resistance | ≥300Ω |
| Basic parameters | |
| Suplay ning kuryenti | 20-35DC |
| Pamangamit king kuryenti | ≤45mA24V power supply, 20mA output |
| Impulse width | ≥2μs |
| Katuliran ning pamaglual | 0.1% FS |
| Ing pamagbayu ning temperatura | 0.01% FS/C Para kareng detalye ning input signal fault detection function, lawan me ing applicable manual |
| Temperatura ning obra | -20°C~+60°C |
| temperatura ning pamitipun | -40°C~+80°C |
| Relatibung humidity | 10%~95%RH (Alang condensation) |
| EMC | Agpang keng GB/T 18268(IEC 61326-1) |
| Lakas ning insulasyon | pilatan ning intrinsically safe side ampo non-intrinsicallysafe side ≥2500V AC/min |
| Insulation resistance | ≥100MΩ(pilatan ning input/output/power supply) |
| kailangan ing kawad | Cross-section≥0.5mm² Insulation strength≥500V |
| Lugar ning pamag-install | Maka-install ya keng safe zone, malyari yang ikonekta kareng intrinsic safety instruments kareng hazardous a lugal angga keng Zone 0, IIC, Zone 20, ampo IIIC |
| Applicable field equipments | Level impulse signal |
| Sertipikasyun ning kaligtasan | |
| Markang e malyaring sabog | [Ex to Ga] IIC [Ex to Da] IIIC |
| Pamantayan a e makasabog | GB/T 3836.1-2021, GB/T 3836.4-2021 |
| Terminals 5-6 | Um=250V AC/DC,Uo=14V DC,Io=8mA, Po=28mW,Co=0.73μF,Lo=150mH |
| katawan ning sertipikasyun | Shanghai Inspection and Testing Institute of Instruments and Automation Systems (SITIIAS) |

NOTE:1、PHD-11TP-11 ali ya kayabe ing output part 2 2、Ing power rail function metung yang optional a function, at kailangan lang i-specify deng gagamit ing paralan ning power supply nung mag-order la. Ing pamili kareng power rail connectors malyari yang lumawe keng page 89 ning "Annex"