- Terminal Board
- Makabukud a Safety Barriers
- Signal Isolators
- Surge Protective Devices
- Safety Relays
- Isolated Intelligent I/O Modules
- Intelligent Gateways
- Industrial Data Optical Transceivers
- Online Dew Point Analyzers
- Data Acquisition Modules
- HART data converter
0102030405
PHD-11TM-11
Overview
Ing signal ning vibration sensor milub ya keng isolated safety barrier, na maka-realize keng 1: 1 isolated transmission ning negative voltage signal output ning vibration sensor keng delikadung lugal papunta keng safe area, ampo malyari yang mag-transmit AC ampo DC signals, na atin matas a anti-interference function. Ing circuit mamye yang isolated power supply para kareng field instruments.
Ing produktung ini mangailangan yang independenting power supply, at ing power supply, input ampo output makabukud la.
| Input keng mapanganib a lugal | |
| Input signal | -20V--0.5V |
| Distribution voltage | Open circuit voltage >-25V ampo 20mA: ≤-18V |
| Safety side output: | |
| Output signal | -20V--0.5V |
| Lalaban keng karga | RL≥20kΩ |
| Supply voltage | 20-35VDC |
| Pamangamit king kuryenti | ≤60mA (24VDC power supply, nung 20mA) |
| LED indicator | Green: Power indicator |
| DC transmission accuracy | |
| AC transmission accuracy | 0Hz~1kHz,±1% |
| 1kHz~10kHz,-2%~+1% | |
| 10kHz~20kHz,-5%~+1% | |
| pakibat ning yugtu | mas ditak keng 10 μ S katumbas ne ning |
| -0.72° 200Hz | |
| -2° 600HZ | |
| -3.6° 1kHz | |
| -36° 10kHz | |
| -72° 20kHz | |
| Parameters ning temperatura | Temperatura ning obra: -20°C~+60°C |
| temperatura ning pamitipun:-40°C~+80°C | |
| Relatibung humidity | 10%~95% RH alang condensation |
| Dielectric strength | pilatan ning intrinsically safe side ampo non-intrinsically safe side (≥ 3000VAC/min); |
| pilatan ning suplay ning kuryenti ampo ing e ligtas a terminal (≥ 1500VAC/min) | |
| Insulation resistance | ≥100MΩ (pilatan ning input/output/power supply) |
| Electromagnetic compatibility | Agpang keng IEC 61326-1(GB/T 18268), IEC 61326-3-1 |
| MTBF | 100000h |
| kailangan ing kawad | Cross section ≥ 0.5mm2; Insulation strength ≥ 500V |
| Applicable field equipments | Vibration sensor, negative voltage generator |
| Lugar ning pamag-install | Maka-install ya keng safe zone, malyari yang ikonekta kareng intrinsic safety instruments kareng hazardous a lugal angga keng Zone 0, IIC, Zone 20, ampo IIIC |
| Sertipikasyun ning kaligtasan | |
| Markang e malyaring sabog | [Ex ia Ga]lIC [Ex ia Da]lllC |
| Pamantayan a e makasabog | GB/T3836.1-2021 GB/T3836.4-2021 |
| Terminals4-5-6 | Um:250V AC/DC Uo=26.5V DC Io=93mA |
| Po=0.687mW Co=0.095μF Lo=4.2mH | |
| katawan ning sertipikasyun | CQST(China National Quality Supervision and Test Center for Explosion Protected Electrical Products) |



PHD-11TC-33A-23