PHD-22TZ-*1*1
Conspectus
| Codex | exemplar RTD | Spatium mensurae | Spatium minimum | Accuratio conversionis |
| 1 | G53 | -50~150℃ | 20℃ | 0.2℃/0.1% |
| Duo | Cu50 | -50~150℃ | 20℃ | 0.2℃/0.1% |
| quattuor | Pt100 | -200~850℃ | 20℃ | 0.2℃/0.1% |
| sex | Pt1000 | -200~850℃ | 20℃ | 0.2℃/0.1% |
| VII | Ni1000 | -60~250℃ | 20℃ | 0.2℃/0.1% |
| Specificationes | |
| Input inpericulosusregio | |
| Signum ingressus | Signa thermistoris duorum filorum vel trium filorum (vide "Tabellam Typi et Ambitus Signi Ingressus" pro singulis) |
| Disiunctio input | "Indicium alarmi" implicitum per programmata configurationis ad "indicium alarmi" mutari potest. |
| Ambitus signalis | Spatium mensurae correspondens resistentiae thermalis |
| Spatium mensurae | Usus configurationem suam ipsi faciunt cum ordinant, eamque in numero caudae vel aliter indicant. |
| Exitus lateris securitatis: | |
| Signum egressus | 4~20mA |
| Capacitas oneris producti | 0~500Ω (configurabilis) Typus egressus tensionis optionalis, resistentia oneris RL ≥ 330kΩ |
| Tensio Alimentaria | 20-35VDC |
| Consumptio energiae | ≤ 90mA (cum copia potentiae 24VDC, (exitus 20mA) |
| Indicator LED | Viridis: Indicator potentiae Lumen flavum alarmis infimi intervalli accensum, lumen rubrum alarmis infimi intervalli accensum |
| Accuratio exitus | Vide "Tabellam Typi et Spatii Signi Ingressus" pro singulis. |
| Tempus responsionis | Ad 90% valoris finalis intra 300ms perveniens |
| Deviatio temperaturae | 0.005% FS/℃ |
| Parametri temperaturae | Temperatura operandi: -20Celsius~+60Celsius temperatura repositionis: -40Celsius~+80Celsius |
| Humiditas relativa | 10%~95% RH nulla condensatio |
| Robur dielectricum | Inter latus intrinsece tutum et latus non intrinsece tutum (≥ 3000VAC/min); inter fontem potentiae et terminale non intrinsecus tutum (≥ 1500VAC/min) |
| Resistentia insulationis | ≥100MΩ (inter input/output/power supply) |
| Compatibilitas electromagnetica | Secundum IEC 61326-1 (GB/T 18268), IEC 61326-3-1 |
| MTBF | 100000h |
| Requisita filorum | Sectio transversalis ≥ 0.5mm2; Robur insulationis ≥ 500V |
| Instrumenta agrorum applicabilia | Thermistores duorum filorum vel trium filorum G53, Cu50, Pt100, Pt1000, Ni1000 |
| Locus institutionis | In zona tuta installatum, instrumentis securitatis intrinsecae in locis periculosis usque ad Zonam 0, IIC, Zonam 20, et IIIC coniungi potest. |
Certificatio securitatis
Certificatio securitatis functionalis | SIL2 secundum normas IEC 61508 |
Signum explosionibus resistens | [Ex ia Ga] IIC [Ex ia Da] C . |
Norma explosionis resistentis | GB/T 3836.1-221 GB/T 3836.4-2021 |
Terminales 1-3, 2-3, 4-6, 5-6 | Um: 250V AC/DC Uo = 8.4V DC Io = 31mA |
Corpus certificationis: | CQST (Centrum Nationale Sinense Supervisionis Qualitatis et Probationis pro Productis Electricis Explosionibus Protectis) |

Nota: 1. Functio ferriviae potentiae functio facultativa est, et usores specificare debent. modus alimentationis electricae cum ordinem ponis
Delectus coniunctorum ferriviae electricae ad paginam 89 "Annexi" referri potest.
2. Cum RTD trium filorum immittitur, necesse est curare ut tres Fila, quantum fieri potest, aequalia sunt longitudinis
3. Cum RTD duorum filorum immittitur, terminales 5 et 6 (2 et 3) claustri securitatis... circuitu brevi poni debet