terminal motherboard PHHS-16AI-M
AI Isolation Backplane PHHS-16AI-M
Number of channels: 16
Mode: two-wire AI, three isolation
Signal type: 2W\3W transmitter and 4W signal (current) with instrument distribution, RTD\TC
With MTL standard HART interface (required to declare before ordering)
Online test port(using XT801 tester)
Installation form: M5 screw fixing or 35mm rail installation
Matching card: C300 & 8-Serial 16AI card
Supporting barrier: Pinghe series Single AI barrier, see the barrier instructions for details
Supporting isolator: Pinghe series Single AI isolator, see the isolator manual for details
Common configurations:
Single input isolation barrier: PHD-11HD-21(with power distribution, supporting 2/4-wire instrument), PHD-11HD-21 (supporting 4-wire HART)
Dual temperature barrier: PHD-11HZ-*1/PHD-11HT-*1
Power supply:
This product is designed for redundant power supply, with power loss alarm output.
Note
The single line (marked with TB2-1 or COM) on the special cable shall be connected to TB2-1 or TB2-4.
Parameter
Order model
PHHS-16AI-M
Description
16-ch AI backplane
Technical parameters
Number of channels
16
Supply voltage
22 ~ 30VDC redundant power supply
Power loss alarm output
Normal close
Sys connection
D-SUB37P
Power connection type
Screw
Terminal crimp specification
0.3~2(mm2)
Signal type
2/3W transmitter, 4W signal Temperature
Complete with barrier
PHD-11HD-21/PHD-11HZ-*1/PHD-11HT-*1 /PHD-11HZ-*1/PHD-11HT-*1
Barrier output signal
4-20mA
Operating temperature
-40˚C~+55˚C
Storage temperature
-40˚C~+70˚C
Dimensions (L*W*H)
292X174x70mm
Install the screws
Hole spacing
M5 4PCS
279.4*101.6mm
Enclose
PS fuse
2Aφ5 glass tube
Matching cable
Standard model
FL-37DS-23A32+1-HON32-ADI-Xm
Simple model
FL-37DS-23A32+1-H32-ADI-Xm
Loose line model
FL-37DS-23A32+1-H-ADI-Xm
Note: Horney terminal board shall be provided by the customer for X-length simple model
Order model |
PHHS-16AI-M |
Description |
16-ch AI backplane |
Technical parameters | |
Number of channels |
16 |
Supply voltage |
22 ~ 30VDC redundant power supply |
Power loss alarm output |
Normal close |
Sys connection |
D-SUB37P |
Power connection type |
Screw |
Terminal crimp specification |
0.3~2(mm2) |
Signal type |
2/3W transmitter, 4W signal Temperature |
Complete with barrier |
PHD-11HD-21/PHD-11HZ-*1/PHD-11HT-*1 /PHD-11HZ-*1/PHD-11HT-*1 |
Barrier output signal |
4-20mA |
Operating temperature |
-40˚C~+55˚C |
Storage temperature |
-40˚C~+70˚C |
Dimensions (L*W*H) |
292X174x70mm |
Install the screws Hole spacing |
M5 4PCS 279.4*101.6mm |
Enclose |
|
PS fuse |
2Aφ5 glass tube |
Matching cable | |
Standard model |
FL-37DS-23A32+1-HON32-ADI-Xm |
Simple model |
FL-37DS-23A32+1-H32-ADI-Xm |
Loose line model |
FL-37DS-23A32+1-H-ADI-Xm |
Note: Horney terminal board shall be provided by the customer for X-length simple model |