- Isolated Safety Barriers
- Signal Isolators
- Surge Protective Devices
- Safety Relays
- Isolated Intelligent I/O Modules
- Intelligent Gateways
- Industrial Data Optical Transceivers
- Online Dew Point Analyzers
- Data Acquisition Modules
- HART data converter
0102030405
PHL-T5-L2
Product overview
12.4mm ultra-thin design;
Surge protection modules are hot pluggable, no desconnection after unplugging;
Surge protective module can be individually detected, convenient to maintain;
Suitable for TC, RTD, CAN, RS485, RS422 and other floating signals circuit ;
Earthing through DIN35 metal rail.
Product specification
Technical data | Two-wire | Three-wire | Four-wire |
RatedoperatingUvnoltage Un | 5V | 5V | 5V |
MaximumoperUatcing voltage Uc | 6V | 6V | 6V |
Nominal operating current IL | 1A | 1A | 1A |
Nominal discharge current In (8 / 20μs) | 10kA | 10kA | 10kA |
The maximum discharge current (8 / 20μs) | 20kA | 20kA | 20kA |
Lightning surge current limp (10 / 350μs) | 2.5kA | 2.5kA | 2.5kA |
Total lightning surge current (10 / 350μs) | 5kA | 7.5kA | 10kA |
Protection voltage Up (8 / 20μs) line-to-line / line to ground | 40V/600V | 40V/600V | 40V/600V |
Protection voltage Up (1KV / μs) line to line / line to ground | 20V/600V | 20V/600V | 20V/600V |
Bandwidth (-0.5dB) | 10MHz | 10MHz | 10MHz |
Response time | 1ns | 1ns | 1ns |
Series resistance (per line) | 1Ω | 1Ω | 1Ω |
Leakage current | <10µA | <10µA | <10µA |
Degrees of protection provided by enclosure (in line with IEC 60529) | IP 20 | IP 20 | IP 20 |
Housing material / Flame retardant grade (the UL94) | PC/V0 | PC/V0 | PC/V0 |
Test standard | GB/T 18802.21 / IEC61643-21 | GB/T 18802.21 / IEC61643-21 | GB/T 18802.21 / IEC61643-21 |
Working temperature range | -40 ℃ ~ +80 ℃ | -40 ℃ ~ +80 ℃ | -40 ℃ ~ +80 ℃ |
Diagram
Dimension drawings