Overview
The thermocouple input isolation safety barrier with surge protection function can transmit the millivolt signal from thermocouple (TC) in the dangerous area to the safe area in 1: 1.
This product requires independent power supply, with isolated power supply, input, and output terminals.
"*" represents the input type of the thermocouple, and the specific model is represented by a code (see "Input Signal Type and Range Table" for details).
Input signal types and measurement range |
||||
Code |
TC model |
Measurement range |
Minimum range |
Conversion accuracy |
1 |
K |
-200~1370℃ |
50℃ |
0.5℃/0.1% |
2 |
S |
-50~1760℃ |
500℃ |
1.5℃/0.1% |
3 |
E |
-140~1000℃ |
50℃ |
0.5℃/0.1% |
4 |
J |
-160~1200℃ |
50℃ |
0.5℃/0.1% |
5 |
B |
250~1800℃ |
500℃ |
1.5℃/0.1% |
6 |
T |
-200~400℃ |
50℃ |
0.5℃/0.1% |
7 |
R |
-50~1760℃ |
500℃ |
1.5℃/0.1% |
8 |
N |
-200~1300℃ |
50℃ |
0.5℃/0.1% |
Input in harzadous area | |
Input signal | K, S, E, J, B, T, R, N thermocouple signals (see "Input Signal Type and Range Table" for details) |
Signal range | The measuring range of the corresponding thermocouple is -5~60mV. |
Safety side output: | |
Output signal | Thermocouple 1: 1 |
Surge protection features: | |
Nominal discharge current ln(8/20μs) | 5kA |
Voltage protection level Up(8/20μs): | 60V(line to line) |
Voltage protection level Up(8/20μs): | 600V(line to ground) |
According to standards | GB/T18802.21-2016(equivalent to 1EC61643-21:2012) |
LED indicator | Green: Power indicator |
Output accuracy | Please refer to the "Input Signal Type and Range Table" for details |
Response time | Reaching 90% of the final value within 300ms |
Temperature drift | 0.005%F.S/℃ |
Temperature parameters | Working temperature: -20℃~+60℃, storage temperature:-40℃~+80℃ |
Relative humidity | 10%~95% RH no condensation |
Dielectric strength | Between intrinsically safe side and non-intrinsically safe side (≥ 3000VAC/min); |
between power supply and non-intrinsically safe terminal (≥ 1500VAC/min) | |
Insulation resistance | ≥100MΩ (between input/output/power supply) |
Electromagnetic compatibility | According to IEC 61326-1(GB/T 18268), IEC 61326-3-1 |
MTBF | 100000h |
Wire requirements | Horizontal cutting surface ≥ 0.5mm2; Insulation strength ≥ 500V |
Applicable field equipments | K. S, E, J, B, T, R, N TC sensors |
Installation place | Installed in a safe zone, it can be connected to intrinsic safety instruments in hazardous areas up to Zone 0, IIC, Zone 20, and IIIC |
Intrinsically safe certification | |
Explosion proof mark | [Ex ia Ga]lIC [Ex ia Da]lllC |
Explosion-proof standard | GB/T3836.1-2021 GB/T3836.4-2021 |
Terminals 3-4 | Um:250V AC/DC Uo=8.4V DC lo=31mA |
Po=65.1mW Co=4.8μF Lo=20mH | |
Certification body | CQST(China National Quality Supervision and Test Centre for Explosion Protected Electrical Products) |
PHD-11TC-33A-23